580 kW to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 580 kW on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)656.59 AAt 1.0 PF: 558.11 A
Active / Apparent Power580.0 kW682.35 kVA · 359.45 kVAR
Recommended Breaker1000 A (NEC)700 A (IEC Nominal)
Recommended Copper Wire2× 1000 kcmil (Parallel)IEC Metric: 2× 400 mm²

Engineering Breakdown for 580 kW at 600V

Input Rating580 kW (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)656.59 Amps
Amperage at 1.00 Power Factor (Resistive Load)558.11 Amps
Real Power (kW / Watts)580.0 kW (580,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)682.35 kVA / 359.45 kVAR
Equivalent Mechanical Horsepower (HP)777.79 HP
NEC 125% Continuous Circuit Breaker1000 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)2× 1000 kcmil (Parallel) (NEC) / 2× 400 mm² (IEC)

Frequently Asked Questions

How many amps is 580 kW at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 580 kW equals 656.59 Amps at an industrial power factor of 0.85 (or 558.11 Amps at unity power factor 1.0).

What size breaker and wire is needed for 580 kW at 600V?

For 656.59A continuous load, NEC requires a 125% rated breaker of 1000A with 2× 1000 kcmil (Parallel) copper conductors, while IEC standard sizing uses a 700A breaker with 2× 400 mm² copper cable.