6 kW to Amps at 208V Single-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 6 kW on a 208V Single-Phase AC circuit.

Line Current (0.85 PF)33.94 AAt 1.0 PF: 28.85 A
Active / Apparent Power6.0 kW7.06 kVA · 3.72 kVAR
Recommended Breaker45 A (NEC)35 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 10 mm²

Engineering Breakdown for 6 kW at 208V

Input Rating6 kW (208V Single-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)33.94 Amps
Amperage at 1.00 Power Factor (Resistive Load)28.85 Amps
Real Power (kW / Watts)6.0 kW (6,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)7.06 kVA / 3.72 kVAR
Equivalent Mechanical Horsepower (HP)8.05 HP
NEC 125% Continuous Circuit Breaker45 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 10 mm² (IEC)

Frequently Asked Questions

How many amps is 6 kW at 208V (1-Phase)?

At 208V Single-Phase AC, 6 kW equals 33.94 Amps at an industrial power factor of 0.85 (or 28.85 Amps at unity power factor 1.0).

What size breaker and wire is needed for 6 kW at 208V?

For 33.94A continuous load, NEC requires a 125% rated breaker of 45A with 8 AWG copper conductors, while IEC standard sizing uses a 35A breaker with 10 mm² copper cable.