78 kW to Amps at 480V Three-Phase AC (US Industrial)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 78 kW on a 480V Three-Phase AC (US Industrial) circuit.

Line Current (0.85 PF)110.38 AAt 1.0 PF: 93.82 A
Active / Apparent Power78.0 kW91.76 kVA · 48.34 kVAR
Recommended Breaker150 A (NEC)125 A (IEC Nominal)
Recommended Copper Wire2 AWGIEC Metric: 35 mm²

Engineering Breakdown for 78 kW at 480V

Input Rating78 kW (480V Three-Phase AC (US Industrial))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)110.38 Amps
Amperage at 1.00 Power Factor (Resistive Load)93.82 Amps
Real Power (kW / Watts)78.0 kW (78,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)91.76 kVA / 48.34 kVAR
Equivalent Mechanical Horsepower (HP)104.6 HP
NEC 125% Continuous Circuit Breaker150 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)2 AWG (NEC) / 35 mm² (IEC)

Frequently Asked Questions

How many amps is 78 kW at 480V (3-Phase)?

At 480V Three-Phase AC (US Industrial), 78 kW equals 110.38 Amps at an industrial power factor of 0.85 (or 93.82 Amps at unity power factor 1.0).

What size breaker and wire is needed for 78 kW at 480V?

For 110.38A continuous load, NEC requires a 125% rated breaker of 150A with 2 AWG copper conductors, while IEC standard sizing uses a 125A breaker with 35 mm² copper cable.