9 kW to Amps at 230V Single-Phase AC (IEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 9 kW on a 230V Single-Phase AC (IEC) circuit.

Line Current (0.85 PF)46.04 AAt 1.0 PF: 39.13 A
Active / Apparent Power9.0 kW10.59 kVA · 5.58 kVAR
Recommended Breaker60 A (NEC)50 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 10 mm²

Engineering Breakdown for 9 kW at 230V

Input Rating9 kW (230V Single-Phase AC (IEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)46.04 Amps
Amperage at 1.00 Power Factor (Resistive Load)39.13 Amps
Real Power (kW / Watts)9.0 kW (9,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)10.59 kVA / 5.58 kVAR
Equivalent Mechanical Horsepower (HP)12.07 HP
NEC 125% Continuous Circuit Breaker60 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 10 mm² (IEC)

Frequently Asked Questions

How many amps is 9 kW at 230V (1-Phase)?

At 230V Single-Phase AC (IEC), 9 kW equals 46.04 Amps at an industrial power factor of 0.85 (or 39.13 Amps at unity power factor 1.0).

What size breaker and wire is needed for 9 kW at 230V?

For 46.04A continuous load, NEC requires a 125% rated breaker of 60A with 8 AWG copper conductors, while IEC standard sizing uses a 50A breaker with 10 mm² copper cable.