⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

9 kW to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 9 kW on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)10.19 AAt 1.0 PF: 8.66 A
Active / Apparent Power9.0 kW10.59 kVA · 5.58 kVAR
Recommended Breaker13 A (NEC)13 A (IEC Nominal)
Recommended Copper Wire14 AWGIEC Metric: 1.5 mm²

Engineering Breakdown for 9 kW at 600V

Input Rating9 kW (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)10.19 Amps
Amperage at 1.00 Power Factor (Resistive Load)8.66 Amps
Real Power (kW / Watts)9.0 kW (9,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)10.59 kVA / 5.58 kVAR
Equivalent Mechanical Horsepower (HP)12.07 HP
NEC 125% Continuous Circuit Breaker13 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)14 AWG (NEC) / 1.5 mm² (IEC)

Frequently Asked Questions

How many amps is 9 kW at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 9 kW equals 10.19 Amps at an industrial power factor of 0.85 (or 8.66 Amps at unity power factor 1.0).

What size breaker and wire is needed for 9 kW at 600V?

For 10.19A continuous load, NEC requires a 125% rated breaker of 13A with 14 AWG copper conductors, while IEC standard sizing uses a 13A breaker with 1.5 mm² copper cable.