98 kW to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 98 kW on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)110.94 AAt 1.0 PF: 94.3 A
Active / Apparent Power98.0 kW115.29 kVA · 60.73 kVAR
Recommended Breaker150 A (NEC)125 A (IEC Nominal)
Recommended Copper Wire2 AWGIEC Metric: 35 mm²

Engineering Breakdown for 98 kW at 600V

Input Rating98 kW (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)110.94 Amps
Amperage at 1.00 Power Factor (Resistive Load)94.3 Amps
Real Power (kW / Watts)98.0 kW (98,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)115.29 kVA / 60.73 kVAR
Equivalent Mechanical Horsepower (HP)131.42 HP
NEC 125% Continuous Circuit Breaker150 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)2 AWG (NEC) / 35 mm² (IEC)

Frequently Asked Questions

How many amps is 98 kW at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 98 kW equals 110.94 Amps at an industrial power factor of 0.85 (or 94.3 Amps at unity power factor 1.0).

What size breaker and wire is needed for 98 kW at 600V?

For 110.94A continuous load, NEC requires a 125% rated breaker of 150A with 2 AWG copper conductors, while IEC standard sizing uses a 125A breaker with 35 mm² copper cable.