Kabeltverrsnitt for 110 Ampere ved 350 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 110 A over 350 m ved 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 6.87V (2.99%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.8V (2.95%)
Voltage at Load223.1 VLine Loss: 755.2 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1098.53 V (477.62%)0.0 V1812.07 V (787.86%)120838.7 WDrop High
2.5 mm²24 A18 A659.12 V (286.57%)0.0 V1087.24 V (472.71%)72503.2 WDrop High
4 mm²32 A25 A411.95 V (179.11%)0.0 V679.52 V (295.45%)45314.5 WDrop High
6 mm²41 A32 A274.63 V (119.41%)0.0 V453.02 V (196.96%)30209.7 WDrop High
10 mm²57 A44 A164.78 V (71.64%)65.2 V271.81 V (118.18%)18125.8 WDrop High
16 mm²76 A59 A102.99 V (44.78%)127.0 V169.88 V (73.86%)11328.6 WDrop High
25 mm²101 A78 A65.91 V (28.66%)164.1 V108.72 V (47.27%)7250.3 WDrop High
35 mm²125 A97 A47.08 V (20.47%)182.9 V77.66 V (33.77%)5178.8 WDrop High
50 mm²151 A118 A32.96 V (14.33%)197.0 V54.36 V (23.64%)3625.2 WDrop High
70 mm²192 A150 A23.54 V (10.23%)206.5 V38.83 V (16.88%)2589.4 WDrop High
95 mm²232 A181 A17.35 V (7.54%)212.7 V28.61 V (12.44%)1908.0 WDrop High
120 mm²269 A210 A13.73 V (5.97%)216.3 V22.65 V (9.85%)1510.5 WDrop High
150 mm²309 A241 A10.99 V (4.78%)219.0 V18.12 V (7.88%)1208.4 W~ ≤5%
185 mm²353 A275 A8.91 V (3.87%)221.1 V14.69 V (6.39%)979.8 W~ ≤5%
240 mm²415 A324 A6.87 V (2.99%)223.1 V11.33 V (4.92%)755.2 W✓ OK (≤3%)
300 mm²477 A372 A5.49 V (2.39%)224.5 V9.06 V (3.94%)604.2 W✓ OK (≤3%)
400 mm²570 A445 A4.12 V (1.79%)225.9 V6.8 V (2.95%)453.1 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 110 Ampere ved 350 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 110A over 350 meter (230V)?

Etter NEK 400 anbefales 240 mm² kobberkabel for 110A ved 350 meter (230V), som gir et spenningsfall på 6.87V (2.99%).

Hvor mange kW tåler 110A ved 230V?

Kursen leverer opptil 25.3 kW med 110A vern.