Kabeltverrsnitt for 16 Ampere ved 15 Meter (230V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 16 A over 15 m ved 230V.
Copper Cable (≤3% Drop)1.5 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 6.78V (2.95%)
Voltage at Load223.2 VLine Loss: 109.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 6.85 V (2.98%) | 223.2 V | 11.3 V (4.91%) | 109.6 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 4.11 V (1.79%) | 225.9 V | 6.78 V (2.95%) | 65.7 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 2.57 V (1.12%) | 227.4 V | 4.24 V (1.84%) | 41.1 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 1.71 V (0.74%) | 228.3 V | 2.82 V (1.23%) | 27.4 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.03 V (0.45%) | 229.0 V | 1.69 V (0.74%) | 16.4 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.64 V (0.28%) | 229.4 V | 1.06 V (0.46%) | 10.3 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.41 V (0.18%) | 229.6 V | 0.68 V (0.29%) | 6.6 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.29 V (0.13%) | 229.7 V | 0.48 V (0.21%) | 4.7 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.21 V (0.09%) | 229.8 V | 0.34 V (0.15%) | 3.3 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.15 V (0.06%) | 229.9 V | 0.24 V (0.11%) | 2.3 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.11 V (0.05%) | 229.9 V | 0.18 V (0.08%) | 1.7 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.09 V (0.04%) | 229.9 V | 0.14 V (0.06%) | 1.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.07 V (0.03%) | 229.9 V | 0.11 V (0.05%) | 1.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.06 V (0.02%) | 229.9 V | 0.09 V (0.04%) | 0.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.04 V (0.02%) | 230.0 V | 0.07 V (0.03%) | 0.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.03 V (0.01%) | 230.0 V | 0.06 V (0.02%) | 0.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.03 V (0.01%) | 230.0 V | 0.04 V (0.02%) | 0.4 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 16 Ampere ved 15 Meter (230V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 16A over 15 meter (230V)?
Etter NEK 400 anbefales 1.5 mm² kobberkabel for 16A ved 15 meter (230V), som gir et spenningsfall på 6.85V (2.98%).
Hvor mange kW tåler 16A ved 230V?
Kursen leverer opptil 3.68 kW med 16A vern.
Related Lengths & Currents (230V)
16A · 5m (230V)16A · 10m (230V)16A · 20m (230V)16A · 25m (230V)16A · 30m (230V)16A · 35m (230V)16A · 40m (230V)16A · 45m (230V)16A · 50m (230V)16A · 60m (230V)16A · 70m (230V)10A · 15m (230V)20A · 15m (230V)25A · 15m (230V)32A · 15m (230V)40A · 15m (230V)50A · 15m (230V)63A · 15m (230V)80A · 15m (230V)100A · 15m (230V)125A · 15m (230V)160A · 15m (230V)200A · 15m (230V)