⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 16 Ampere ved 40 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 16 A over 40 m ved 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 4.52V (1.96%)
Voltage at Load223.2 VLine Loss: 109.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A18.26 V (7.94%)211.7 V30.12 V (13.1%)292.2 WDrop High
2.5 mm²24 A18 A10.96 V (4.76%)219.0 V18.07 V (7.86%)175.3 W~ ≤5%
4 mm²32 A25 A6.85 V (2.98%)223.2 V11.3 V (4.91%)109.6 W✓ OK (≤3%)
6 mm²41 A32 A4.57 V (1.98%)225.4 V7.53 V (3.27%)73.0 W✓ OK (≤3%)
10 mm²57 A44 A2.74 V (1.19%)227.3 V4.52 V (1.96%)43.8 W✓ OK (≤3%)
16 mm²76 A59 A1.71 V (0.74%)228.3 V2.82 V (1.23%)27.4 W✓ OK (≤3%)
25 mm²101 A78 A1.1 V (0.48%)228.9 V1.81 V (0.79%)17.5 W✓ OK (≤3%)
35 mm²125 A97 A0.78 V (0.34%)229.2 V1.29 V (0.56%)12.5 W✓ OK (≤3%)
50 mm²151 A118 A0.55 V (0.24%)229.5 V0.9 V (0.39%)8.8 W✓ OK (≤3%)
70 mm²192 A150 A0.39 V (0.17%)229.6 V0.65 V (0.28%)6.3 W✓ OK (≤3%)
95 mm²232 A181 A0.29 V (0.13%)229.7 V0.48 V (0.21%)4.6 W✓ OK (≤3%)
120 mm²269 A210 A0.23 V (0.1%)229.8 V0.38 V (0.16%)3.7 W✓ OK (≤3%)
150 mm²309 A241 A0.18 V (0.08%)229.8 V0.3 V (0.13%)2.9 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.06%)229.9 V0.24 V (0.11%)2.4 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.05%)229.9 V0.19 V (0.08%)1.8 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.04%)229.9 V0.15 V (0.07%)1.5 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.03%)229.9 V0.11 V (0.05%)1.1 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 16 Ampere ved 40 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 16A over 40 meter (230V)?

Etter NEK 400 anbefales 4 mm² kobberkabel for 16A ved 40 meter (230V), som gir et spenningsfall på 6.85V (2.98%).

Hvor mange kW tåler 16A ved 230V?

Kursen leverer opptil 3.68 kW med 16A vern.