Kabeltverrsnitt for 16 Ampere ved 30 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 16 A over 30 m ved 400V.
Copper Cable (≤3% Drop)1.5 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 11.74V (2.93%)
Voltage at Load388.1 VLine Loss: 328.7 W
Max Power & Breaker11.09 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 30m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 11.86 V (2.97%) | 388.1 V | 19.57 V (4.89%) | 328.7 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 7.12 V (1.78%) | 392.9 V | 11.74 V (2.93%) | 197.2 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 4.45 V (1.11%) | 395.6 V | 7.34 V (1.83%) | 123.3 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 2.97 V (0.74%) | 397.0 V | 4.89 V (1.22%) | 82.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.78 V (0.44%) | 398.2 V | 2.93 V (0.73%) | 49.3 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.11 V (0.28%) | 398.9 V | 1.83 V (0.46%) | 30.8 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.71 V (0.18%) | 399.3 V | 1.17 V (0.29%) | 19.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.51 V (0.13%) | 399.5 V | 0.84 V (0.21%) | 14.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.36 V (0.09%) | 399.6 V | 0.59 V (0.15%) | 9.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.25 V (0.06%) | 399.7 V | 0.42 V (0.1%) | 7.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.19 V (0.05%) | 399.8 V | 0.31 V (0.08%) | 5.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.15 V (0.04%) | 399.9 V | 0.24 V (0.06%) | 4.1 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.12 V (0.03%) | 399.9 V | 0.2 V (0.05%) | 3.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.1 V (0.02%) | 399.9 V | 0.16 V (0.04%) | 2.7 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.07 V (0.02%) | 399.9 V | 0.12 V (0.03%) | 2.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.06 V (0.01%) | 399.9 V | 0.1 V (0.02%) | 1.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.04 V (0.01%) | 400.0 V | 0.07 V (0.02%) | 1.2 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 16 Ampere ved 30 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 16A over 30 meter (400V)?
Etter NEK 400 anbefales 1.5 mm² kobberkabel for 16A ved 30 meter (400V), som gir et spenningsfall på 11.86V (2.97%).
Hvor mange kW tåler 16A ved 400V?
Kursen leverer opptil 11.09 kW med 16A vern.
Related Lengths & Currents (400V)
16A · 5m (400V)16A · 10m (400V)16A · 15m (400V)16A · 20m (400V)16A · 25m (400V)16A · 35m (400V)16A · 40m (400V)16A · 45m (400V)16A · 50m (400V)16A · 60m (400V)16A · 70m (400V)10A · 30m (400V)20A · 30m (400V)25A · 30m (400V)32A · 30m (400V)40A · 30m (400V)50A · 30m (400V)63A · 30m (400V)80A · 30m (400V)100A · 30m (400V)125A · 30m (400V)160A · 30m (400V)200A · 30m (400V)