Kabeltverrsnitt for 16 Ampere ved 5 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 16 A over 5 m ved 400V.
Copper Cable (≤3% Drop)1.5 mm²Drop: 1.98V (0.49%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 1.96V (0.49%)
Voltage at Load398.0 VLine Loss: 54.8 W
Max Power & Breaker11.09 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1.98 V (0.49%) | 398.0 V | 3.26 V (0.82%) | 54.8 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 1.19 V (0.3%) | 398.8 V | 1.96 V (0.49%) | 32.9 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 0.74 V (0.19%) | 399.3 V | 1.22 V (0.31%) | 20.5 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 0.49 V (0.12%) | 399.5 V | 0.82 V (0.2%) | 13.7 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 0.3 V (0.07%) | 399.7 V | 0.49 V (0.12%) | 8.2 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.19 V (0.05%) | 399.8 V | 0.31 V (0.08%) | 5.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.12 V (0.03%) | 399.9 V | 0.2 V (0.05%) | 3.3 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.08 V (0.02%) | 399.9 V | 0.14 V (0.03%) | 2.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.06 V (0.01%) | 399.9 V | 0.1 V (0.02%) | 1.6 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.04 V (0.01%) | 400.0 V | 0.07 V (0.02%) | 1.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.03 V (0.01%) | 400.0 V | 0.05 V (0.01%) | 0.9 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.02 V (0.01%) | 400.0 V | 0.04 V (0.01%) | 0.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.02 V (0.0%) | 400.0 V | 0.03 V (0.01%) | 0.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.02 V (0.0%) | 400.0 V | 0.03 V (0.01%) | 0.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.01 V (0.0%) | 400.0 V | 0.02 V (0.01%) | 0.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.01 V (0.0%) | 400.0 V | 0.02 V (0.0%) | 0.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.01 V (0.0%) | 400.0 V | 0.01 V (0.0%) | 0.2 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 16 Ampere ved 5 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 16A over 5 meter (400V)?
Etter NEK 400 anbefales 1.5 mm² kobberkabel for 16A ved 5 meter (400V), som gir et spenningsfall på 1.98V (0.49%).
Hvor mange kW tåler 16A ved 400V?
Kursen leverer opptil 11.09 kW med 16A vern.
Related Lengths & Currents (400V)
16A · 10m (400V)16A · 15m (400V)16A · 20m (400V)16A · 25m (400V)16A · 30m (400V)16A · 35m (400V)16A · 40m (400V)16A · 45m (400V)16A · 50m (400V)16A · 60m (400V)16A · 70m (400V)10A · 5m (400V)20A · 5m (400V)25A · 5m (400V)32A · 5m (400V)40A · 5m (400V)50A · 5m (400V)63A · 5m (400V)80A · 5m (400V)100A · 5m (400V)125A · 5m (400V)160A · 5m (400V)200A · 5m (400V)