⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 175 Ampere ved 5 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 175 A over 5 m ved 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 0.46V (0.12%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.56V (0.14%)
Voltage at Load399.5 VLine Loss: 140.4 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A21.62 V (5.41%)378.4 V35.67 V (8.92%)6553.8 WDrop High
2.5 mm²24 A18 A12.97 V (3.24%)387.0 V21.4 V (5.35%)3932.2 WDrop High
4 mm²32 A25 A8.11 V (2.03%)391.9 V13.37 V (3.34%)2457.7 WDrop High
6 mm²41 A32 A5.41 V (1.35%)394.6 V8.92 V (2.23%)1638.4 WDrop High
10 mm²57 A44 A3.24 V (0.81%)396.8 V5.35 V (1.34%)983.1 WDrop High
16 mm²76 A59 A2.03 V (0.51%)398.0 V3.34 V (0.84%)614.4 WDrop High
25 mm²101 A78 A1.3 V (0.32%)398.7 V2.14 V (0.53%)393.2 WDrop High
35 mm²125 A97 A0.93 V (0.23%)399.1 V1.53 V (0.38%)280.9 WDrop High
50 mm²151 A118 A0.65 V (0.16%)399.4 V1.07 V (0.27%)196.6 WDrop High
70 mm²192 A150 A0.46 V (0.12%)399.5 V0.76 V (0.19%)140.4 W✓ OK (≤3%)
95 mm²232 A181 A0.34 V (0.09%)399.7 V0.56 V (0.14%)103.5 W✓ OK (≤3%)
120 mm²269 A210 A0.27 V (0.07%)399.7 V0.45 V (0.11%)81.9 W✓ OK (≤3%)
150 mm²309 A241 A0.22 V (0.05%)399.8 V0.36 V (0.09%)65.5 W✓ OK (≤3%)
185 mm²353 A275 A0.18 V (0.04%)399.8 V0.29 V (0.07%)53.1 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.03%)399.9 V0.22 V (0.06%)41.0 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.03%)399.9 V0.18 V (0.04%)32.8 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.02%)399.9 V0.13 V (0.03%)24.6 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 175 Ampere ved 5 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 175A over 5 meter (400V)?

Etter NEK 400 anbefales 70 mm² kobberkabel for 175A ved 5 meter (400V), som gir et spenningsfall på 0.46V (0.12%).

Hvor mange kW tåler 175A ved 400V?

Kursen leverer opptil 121.24 kW med 175A vern.