Kabeltverrsnitt for 20 Ampere ved 45 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 20 A over 45 m ved 400V.
Copper Cable (≤3% Drop)4 mm²Drop: 8.34V (2.08%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 9.17V (2.29%)
Voltage at Load391.7 VLine Loss: 288.9 W
Max Power & Breaker13.86 kW20A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 45m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 22.24 V (5.56%) | 377.8 V | 36.68 V (9.17%) | 770.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 13.34 V (3.34%) | 386.7 V | 22.01 V (5.5%) | 462.2 W | ~ ≤5% |
| 4 mm² | 32 A | 25 A | 8.34 V (2.08%) | 391.7 V | 13.76 V (3.44%) | 288.9 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 5.56 V (1.39%) | 394.4 V | 9.17 V (2.29%) | 192.6 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 3.34 V (0.83%) | 396.7 V | 5.5 V (1.38%) | 115.6 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 2.08 V (0.52%) | 397.9 V | 3.44 V (0.86%) | 72.2 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.33 V (0.33%) | 398.7 V | 2.2 V (0.55%) | 46.2 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.95 V (0.24%) | 399.0 V | 1.57 V (0.39%) | 33.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.67 V (0.17%) | 399.3 V | 1.1 V (0.28%) | 23.1 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.48 V (0.12%) | 399.5 V | 0.79 V (0.2%) | 16.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.35 V (0.09%) | 399.6 V | 0.58 V (0.14%) | 12.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.28 V (0.07%) | 399.7 V | 0.46 V (0.11%) | 9.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.22 V (0.06%) | 399.8 V | 0.37 V (0.09%) | 7.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.18 V (0.05%) | 399.8 V | 0.3 V (0.07%) | 6.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.14 V (0.03%) | 399.9 V | 0.23 V (0.06%) | 4.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.11 V (0.03%) | 399.9 V | 0.18 V (0.05%) | 3.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.08 V (0.02%) | 399.9 V | 0.14 V (0.03%) | 2.9 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 20 Ampere ved 45 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 20A over 45 meter (400V)?
Etter NEK 400 anbefales 4 mm² kobberkabel for 20A ved 45 meter (400V), som gir et spenningsfall på 8.34V (2.08%).
Hvor mange kW tåler 20A ved 400V?
Kursen leverer opptil 13.86 kW med 20A vern.
Related Lengths & Currents (400V)
20A · 5m (400V)20A · 10m (400V)20A · 15m (400V)20A · 20m (400V)20A · 25m (400V)20A · 30m (400V)20A · 35m (400V)20A · 40m (400V)20A · 50m (400V)20A · 60m (400V)20A · 70m (400V)10A · 45m (400V)16A · 45m (400V)25A · 45m (400V)32A · 45m (400V)40A · 45m (400V)50A · 45m (400V)63A · 45m (400V)80A · 45m (400V)100A · 45m (400V)125A · 45m (400V)160A · 45m (400V)200A · 45m (400V)