Kabeltverrsnitt for 25 Ampere ved 45 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 25 A over 45 m ved 400V.
Copper Cable (≤3% Drop)4 mm²Drop: 10.42V (2.61%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 11.46V (2.87%)
Voltage at Load389.6 VLine Loss: 451.4 W
Max Power & Breaker17.32 kW25A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 45m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 27.8 V (6.95%) | 372.2 V | 45.86 V (11.46%) | 1203.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 16.68 V (4.17%) | 383.3 V | 27.51 V (6.88%) | 722.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 10.42 V (2.61%) | 389.6 V | 17.2 V (4.3%) | 451.4 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 6.95 V (1.74%) | 393.1 V | 11.46 V (2.87%) | 300.9 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 4.17 V (1.04%) | 395.8 V | 6.88 V (1.72%) | 180.6 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 2.61 V (0.65%) | 397.4 V | 4.3 V (1.07%) | 112.9 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.67 V (0.42%) | 398.3 V | 2.75 V (0.69%) | 72.2 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.19 V (0.3%) | 398.8 V | 1.97 V (0.49%) | 51.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.83 V (0.21%) | 399.2 V | 1.38 V (0.34%) | 36.1 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.6 V (0.15%) | 399.4 V | 0.98 V (0.25%) | 25.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.44 V (0.11%) | 399.6 V | 0.72 V (0.18%) | 19.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.35 V (0.09%) | 399.7 V | 0.57 V (0.14%) | 15.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.28 V (0.07%) | 399.7 V | 0.46 V (0.11%) | 12.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.23 V (0.06%) | 399.8 V | 0.37 V (0.09%) | 9.8 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.17 V (0.04%) | 399.8 V | 0.29 V (0.07%) | 7.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.14 V (0.03%) | 399.9 V | 0.23 V (0.06%) | 6.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.1 V (0.03%) | 399.9 V | 0.17 V (0.04%) | 4.5 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 25 Ampere ved 45 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 25A over 45 meter (400V)?
Etter NEK 400 anbefales 4 mm² kobberkabel for 25A ved 45 meter (400V), som gir et spenningsfall på 10.42V (2.61%).
Hvor mange kW tåler 25A ved 400V?
Kursen leverer opptil 17.32 kW med 25A vern.
Related Lengths & Currents (400V)
25A · 5m (400V)25A · 10m (400V)25A · 15m (400V)25A · 20m (400V)25A · 25m (400V)25A · 30m (400V)25A · 35m (400V)25A · 40m (400V)25A · 50m (400V)25A · 60m (400V)25A · 70m (400V)10A · 45m (400V)16A · 45m (400V)20A · 45m (400V)32A · 45m (400V)40A · 45m (400V)50A · 45m (400V)63A · 45m (400V)80A · 45m (400V)100A · 45m (400V)125A · 45m (400V)160A · 45m (400V)200A · 45m (400V)