Kabeltverrsnitt for 200 Ampere ved 45 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 200 A over 45 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 4.05V (1.76%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 5.29V (2.3%)
Voltage at Load225.9 VLine Loss: 810.9 W
Max Power & Breaker46.0 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A256.8 V (111.65%)0.0 V423.6 V (184.17%)51360.0 WDrop High
2.5 mm²24 A18 A154.08 V (66.99%)75.9 V254.16 V (110.5%)30816.0 WDrop High
4 mm²32 A25 A96.3 V (41.87%)133.7 V158.85 V (69.07%)19260.0 WDrop High
6 mm²41 A32 A64.2 V (27.91%)165.8 V105.9 V (46.04%)12840.0 WDrop High
10 mm²57 A44 A38.52 V (16.75%)191.5 V63.54 V (27.63%)7704.0 WDrop High
16 mm²76 A59 A24.07 V (10.47%)205.9 V39.71 V (17.27%)4815.0 WDrop High
25 mm²101 A78 A15.41 V (6.7%)214.6 V25.42 V (11.05%)3081.6 WDrop High
35 mm²125 A97 A11.01 V (4.79%)219.0 V18.15 V (7.89%)2201.1 WDrop High
50 mm²151 A118 A7.7 V (3.35%)222.3 V12.71 V (5.53%)1540.8 WDrop High
70 mm²192 A150 A5.5 V (2.39%)224.5 V9.08 V (3.95%)1100.6 WDrop High
95 mm²232 A181 A4.05 V (1.76%)225.9 V6.69 V (2.91%)810.9 W✓ OK (≤3%)
120 mm²269 A210 A3.21 V (1.4%)226.8 V5.29 V (2.3%)642.0 W✓ OK (≤3%)
150 mm²309 A241 A2.57 V (1.12%)227.4 V4.24 V (1.84%)513.6 W✓ OK (≤3%)
185 mm²353 A275 A2.08 V (0.91%)227.9 V3.43 V (1.49%)416.4 W✓ OK (≤3%)
240 mm²415 A324 A1.6 V (0.7%)228.4 V2.65 V (1.15%)321.0 W✓ OK (≤3%)
300 mm²477 A372 A1.28 V (0.56%)228.7 V2.12 V (0.92%)256.8 W✓ OK (≤3%)
400 mm²570 A445 A0.96 V (0.42%)229.0 V1.59 V (0.69%)192.6 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 200 Ampere ved 45 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 200A over 45 meter (230V)?

Etter NEK 400 anbefales 95 mm² kobberkabel for 200A ved 45 meter (230V), som gir et spenningsfall på 4.05V (1.76%).

Hvor mange kW tåler 200A ved 230V?

Kursen leverer opptil 46.0 kW med 200A vern.