Kabeltverrsnitt for 200 Ampere ved 40 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 200 A over 40 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 3.6V (1.57%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 4.71V (2.05%)
Voltage at Load226.4 VLine Loss: 720.8 W
Max Power & Breaker46.0 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A228.27 V (99.25%)1.7 V376.53 V (163.71%)45653.3 WDrop High
2.5 mm²24 A18 A136.96 V (59.55%)93.0 V225.92 V (98.23%)27392.0 WDrop High
4 mm²32 A25 A85.6 V (37.22%)144.4 V141.2 V (61.39%)17120.0 WDrop High
6 mm²41 A32 A57.07 V (24.81%)172.9 V94.13 V (40.93%)11413.3 WDrop High
10 mm²57 A44 A34.24 V (14.89%)195.8 V56.48 V (24.56%)6848.0 WDrop High
16 mm²76 A59 A21.4 V (9.3%)208.6 V35.3 V (15.35%)4280.0 WDrop High
25 mm²101 A78 A13.7 V (5.95%)216.3 V22.59 V (9.82%)2739.2 WDrop High
35 mm²125 A97 A9.78 V (4.25%)220.2 V16.14 V (7.02%)1956.6 WDrop High
50 mm²151 A118 A6.85 V (2.98%)223.2 V11.3 V (4.91%)1369.6 WDrop High
70 mm²192 A150 A4.89 V (2.13%)225.1 V8.07 V (3.51%)978.3 WDrop High
95 mm²232 A181 A3.6 V (1.57%)226.4 V5.95 V (2.58%)720.8 W✓ OK (≤3%)
120 mm²269 A210 A2.85 V (1.24%)227.1 V4.71 V (2.05%)570.7 W✓ OK (≤3%)
150 mm²309 A241 A2.28 V (0.99%)227.7 V3.77 V (1.64%)456.5 W✓ OK (≤3%)
185 mm²353 A275 A1.85 V (0.8%)228.1 V3.05 V (1.33%)370.2 W✓ OK (≤3%)
240 mm²415 A324 A1.43 V (0.62%)228.6 V2.35 V (1.02%)285.3 W✓ OK (≤3%)
300 mm²477 A372 A1.14 V (0.5%)228.9 V1.88 V (0.82%)228.3 W✓ OK (≤3%)
400 mm²570 A445 A0.86 V (0.37%)229.1 V1.41 V (0.61%)171.2 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 200 Ampere ved 40 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 200A over 40 meter (230V)?

Etter NEK 400 anbefales 95 mm² kobberkabel for 200A ved 40 meter (230V), som gir et spenningsfall på 3.6V (1.57%).

Hvor mange kW tåler 200A ved 230V?

Kursen leverer opptil 46.0 kW med 200A vern.