Kabeltverrsnitt for 25 Ampere ved 20 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 25 A over 20 m ved 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 4.63V (1.16%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 7.64V (1.91%)
Voltage at Load395.4 VLine Loss: 200.6 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.36 V (3.09%)387.6 V20.38 V (5.1%)535.0 WDrop High
2.5 mm²24 A18 A7.41 V (1.85%)392.6 V12.23 V (3.06%)321.0 WDrop High
4 mm²32 A25 A4.63 V (1.16%)395.4 V7.64 V (1.91%)200.6 W✓ OK (≤3%)
6 mm²41 A32 A3.09 V (0.77%)396.9 V5.1 V (1.27%)133.8 W✓ OK (≤3%)
10 mm²57 A44 A1.85 V (0.46%)398.1 V3.06 V (0.76%)80.2 W✓ OK (≤3%)
16 mm²76 A59 A1.16 V (0.29%)398.8 V1.91 V (0.48%)50.2 W✓ OK (≤3%)
25 mm²101 A78 A0.74 V (0.19%)399.3 V1.22 V (0.31%)32.1 W✓ OK (≤3%)
35 mm²125 A97 A0.53 V (0.13%)399.5 V0.87 V (0.22%)22.9 W✓ OK (≤3%)
50 mm²151 A118 A0.37 V (0.09%)399.6 V0.61 V (0.15%)16.1 W✓ OK (≤3%)
70 mm²192 A150 A0.26 V (0.07%)399.7 V0.44 V (0.11%)11.5 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.05%)399.8 V0.32 V (0.08%)8.4 W✓ OK (≤3%)
120 mm²269 A210 A0.15 V (0.04%)399.8 V0.25 V (0.06%)6.7 W✓ OK (≤3%)
150 mm²309 A241 A0.12 V (0.03%)399.9 V0.2 V (0.05%)5.3 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.03%)399.9 V0.17 V (0.04%)4.3 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.02%)399.9 V0.13 V (0.03%)3.3 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.02%)399.9 V0.1 V (0.03%)2.7 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.01%)400.0 V0.08 V (0.02%)2.0 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 25 Ampere ved 20 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 25A over 20 meter (400V)?

Etter NEK 400 anbefales 4 mm² kobberkabel for 25A ved 20 meter (400V), som gir et spenningsfall på 4.63V (1.16%).

Hvor mange kW tåler 25A ved 400V?

Kursen leverer opptil 17.32 kW med 25A vern.