Kabeltverrsnitt for 250 Ampere ved 25 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 250 A over 25 m ved 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 2.23V (0.97%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 2.39V (1.04%)
Voltage at Load227.8 VLine Loss: 557.3 W
Max Power & Breaker57.5 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A178.33 V (77.54%)51.7 V294.17 V (127.9%)44583.3 WDrop High
2.5 mm²24 A18 A107.0 V (46.52%)123.0 V176.5 V (76.74%)26750.0 WDrop High
4 mm²32 A25 A66.87 V (29.08%)163.1 V110.31 V (47.96%)16718.7 WDrop High
6 mm²41 A32 A44.58 V (19.38%)185.4 V73.54 V (31.97%)11145.8 WDrop High
10 mm²57 A44 A26.75 V (11.63%)203.2 V44.12 V (19.18%)6687.5 WDrop High
16 mm²76 A59 A16.72 V (7.27%)213.3 V27.58 V (11.99%)4179.7 WDrop High
25 mm²101 A78 A10.7 V (4.65%)219.3 V17.65 V (7.67%)2675.0 WDrop High
35 mm²125 A97 A7.64 V (3.32%)222.4 V12.61 V (5.48%)1910.7 WDrop High
50 mm²151 A118 A5.35 V (2.33%)224.7 V8.82 V (3.84%)1337.5 WDrop High
70 mm²192 A150 A3.82 V (1.66%)226.2 V6.3 V (2.74%)955.4 WDrop High
95 mm²232 A181 A2.82 V (1.22%)227.2 V4.64 V (2.02%)703.9 WDrop High
120 mm²269 A210 A2.23 V (0.97%)227.8 V3.68 V (1.6%)557.3 W✓ OK (≤3%)
150 mm²309 A241 A1.78 V (0.78%)228.2 V2.94 V (1.28%)445.8 W✓ OK (≤3%)
185 mm²353 A275 A1.45 V (0.63%)228.6 V2.39 V (1.04%)361.5 W✓ OK (≤3%)
240 mm²415 A324 A1.11 V (0.48%)228.9 V1.84 V (0.8%)278.6 W✓ OK (≤3%)
300 mm²477 A372 A0.89 V (0.39%)229.1 V1.47 V (0.64%)222.9 W✓ OK (≤3%)
400 mm²570 A445 A0.67 V (0.29%)229.3 V1.1 V (0.48%)167.2 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 250 Ampere ved 25 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 250A over 25 meter (230V)?

Etter NEK 400 anbefales 120 mm² kobberkabel for 250A ved 25 meter (230V), som gir et spenningsfall på 2.23V (0.97%).

Hvor mange kW tåler 250A ved 230V?

Kursen leverer opptil 57.5 kW med 250A vern.