⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 250 Ampere ved 40 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 250 A over 40 m ved 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 3.57V (1.55%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 3.82V (1.66%)
Voltage at Load226.4 VLine Loss: 891.7 W
Max Power & Breaker57.5 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A285.33 V (124.06%)0.0 V470.67 V (204.64%)71333.3 WDrop High
2.5 mm²24 A18 A171.2 V (74.43%)58.8 V282.4 V (122.78%)42800.0 WDrop High
4 mm²32 A25 A107.0 V (46.52%)123.0 V176.5 V (76.74%)26750.0 WDrop High
6 mm²41 A32 A71.33 V (31.01%)158.7 V117.67 V (51.16%)17833.3 WDrop High
10 mm²57 A44 A42.8 V (18.61%)187.2 V70.6 V (30.7%)10700.0 WDrop High
16 mm²76 A59 A26.75 V (11.63%)203.2 V44.12 V (19.18%)6687.5 WDrop High
25 mm²101 A78 A17.12 V (7.44%)212.9 V28.24 V (12.28%)4280.0 WDrop High
35 mm²125 A97 A12.23 V (5.32%)217.8 V20.17 V (8.77%)3057.1 WDrop High
50 mm²151 A118 A8.56 V (3.72%)221.4 V14.12 V (6.14%)2140.0 WDrop High
70 mm²192 A150 A6.11 V (2.66%)223.9 V10.09 V (4.39%)1528.6 WDrop High
95 mm²232 A181 A4.51 V (1.96%)225.5 V7.43 V (3.23%)1126.3 WDrop High
120 mm²269 A210 A3.57 V (1.55%)226.4 V5.88 V (2.56%)891.7 W✓ OK (≤3%)
150 mm²309 A241 A2.85 V (1.24%)227.1 V4.71 V (2.05%)713.3 W✓ OK (≤3%)
185 mm²353 A275 A2.31 V (1.01%)227.7 V3.82 V (1.66%)578.4 W✓ OK (≤3%)
240 mm²415 A324 A1.78 V (0.78%)228.2 V2.94 V (1.28%)445.8 W✓ OK (≤3%)
300 mm²477 A372 A1.43 V (0.62%)228.6 V2.35 V (1.02%)356.7 W✓ OK (≤3%)
400 mm²570 A445 A1.07 V (0.47%)228.9 V1.76 V (0.77%)267.5 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 250 Ampere ved 40 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 250A over 40 meter (230V)?

Etter NEK 400 anbefales 120 mm² kobberkabel for 250A ved 40 meter (230V), som gir et spenningsfall på 3.57V (1.55%).

Hvor mange kW tåler 250A ved 230V?

Kursen leverer opptil 57.5 kW med 250A vern.