⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 325 Ampere ved 120 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 325 A over 120 m ved 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 5.56V (2.42%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.88V (2.99%)
Voltage at Load224.4 VLine Loss: 1808.3 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1112.8 V (483.83%)0.0 V1835.6 V (798.09%)361660.0 WDrop High
2.5 mm²24 A18 A667.68 V (290.3%)0.0 V1101.36 V (478.85%)216996.0 WDrop High
4 mm²32 A25 A417.3 V (181.43%)0.0 V688.35 V (299.28%)135622.5 WDrop High
6 mm²41 A32 A278.2 V (120.96%)0.0 V458.9 V (199.52%)90415.0 WDrop High
10 mm²57 A44 A166.92 V (72.57%)63.1 V275.34 V (119.71%)54249.0 WDrop High
16 mm²76 A59 A104.33 V (45.36%)125.7 V172.09 V (74.82%)33905.6 WDrop High
25 mm²101 A78 A66.77 V (29.03%)163.2 V110.14 V (47.89%)21699.6 WDrop High
35 mm²125 A97 A47.69 V (20.74%)182.3 V78.67 V (34.2%)15499.7 WDrop High
50 mm²151 A118 A33.38 V (14.51%)196.6 V55.07 V (23.94%)10849.8 WDrop High
70 mm²192 A150 A23.85 V (10.37%)206.2 V39.33 V (17.1%)7749.9 WDrop High
95 mm²232 A181 A17.57 V (7.64%)212.4 V28.98 V (12.6%)5710.4 WDrop High
120 mm²269 A210 A13.91 V (6.05%)216.1 V22.95 V (9.98%)4520.8 WDrop High
150 mm²309 A241 A11.13 V (4.84%)218.9 V18.36 V (7.98%)3616.6 WDrop High
185 mm²353 A275 A9.02 V (3.92%)221.0 V14.88 V (6.47%)2932.4 W~ ≤5%
240 mm²415 A324 A6.96 V (3.02%)223.0 V11.47 V (4.99%)2260.4 W~ ≤5%
300 mm²477 A372 A5.56 V (2.42%)224.4 V9.18 V (3.99%)1808.3 W✓ OK (≤3%)
400 mm²570 A445 A4.17 V (1.81%)225.8 V6.88 V (2.99%)1356.2 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 325 Ampere ved 120 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 325A over 120 meter (230V)?

Etter NEK 400 anbefales 300 mm² kobberkabel for 325A ved 120 meter (230V), som gir et spenningsfall på 5.56V (2.42%).

Hvor mange kW tåler 325A ved 230V?

Kursen leverer opptil 74.75 kW med 350A vern.