Kabeltverrsnitt for 40 Ampere ved 70 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 40 A over 70 m ved 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 4.79V (2.08%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.65V (2.46%)
Voltage at Load225.2 VLine Loss: 191.7 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A79.89 V (34.74%)150.1 V131.79 V (57.3%)3195.7 WDrop High
2.5 mm²24 A18 A47.94 V (20.84%)182.1 V79.07 V (34.38%)1917.4 WDrop High
4 mm²32 A25 A29.96 V (13.03%)200.0 V49.42 V (21.49%)1198.4 WDrop High
6 mm²41 A32 A19.97 V (8.68%)210.0 V32.95 V (14.32%)798.9 WDrop High
10 mm²57 A44 A11.98 V (5.21%)218.0 V19.77 V (8.59%)479.4 WDrop High
16 mm²76 A59 A7.49 V (3.26%)222.5 V12.36 V (5.37%)299.6 W~ ≤5%
25 mm²101 A78 A4.79 V (2.08%)225.2 V7.91 V (3.44%)191.7 W✓ OK (≤3%)
35 mm²125 A97 A3.42 V (1.49%)226.6 V5.65 V (2.46%)137.0 W✓ OK (≤3%)
50 mm²151 A118 A2.4 V (1.04%)227.6 V3.95 V (1.72%)95.9 W✓ OK (≤3%)
70 mm²192 A150 A1.71 V (0.74%)228.3 V2.82 V (1.23%)68.5 W✓ OK (≤3%)
95 mm²232 A181 A1.26 V (0.55%)228.7 V2.08 V (0.9%)50.5 W✓ OK (≤3%)
120 mm²269 A210 A1.0 V (0.43%)229.0 V1.65 V (0.72%)39.9 W✓ OK (≤3%)
150 mm²309 A241 A0.8 V (0.35%)229.2 V1.32 V (0.57%)32.0 W✓ OK (≤3%)
185 mm²353 A275 A0.65 V (0.28%)229.4 V1.07 V (0.46%)25.9 W✓ OK (≤3%)
240 mm²415 A324 A0.5 V (0.22%)229.5 V0.82 V (0.36%)20.0 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (0.17%)229.6 V0.66 V (0.29%)16.0 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (0.13%)229.7 V0.49 V (0.21%)12.0 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 40 Ampere ved 70 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 40A over 70 meter (230V)?

Etter NEK 400 anbefales 25 mm² kobberkabel for 40A ved 70 meter (230V), som gir et spenningsfall på 4.79V (2.08%).

Hvor mange kW tåler 40A ved 230V?

Kursen leverer opptil 9.2 kW med 40A vern.