Kabeltverrsnitt for 32 Ampere ved 70 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 32 A over 70 m ved 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 6.33V (2.75%)
Voltage at Load224.0 VLine Loss: 191.7 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A63.91 V (27.79%)166.1 V105.43 V (45.84%)2045.3 WDrop High
2.5 mm²24 A18 A38.35 V (16.67%)191.7 V63.26 V (27.5%)1227.2 WDrop High
4 mm²32 A25 A23.97 V (10.42%)206.0 V39.54 V (17.19%)767.0 WDrop High
6 mm²41 A32 A15.98 V (6.95%)214.0 V26.36 V (11.46%)511.3 WDrop High
10 mm²57 A44 A9.59 V (4.17%)220.4 V15.81 V (6.88%)306.8 W~ ≤5%
16 mm²76 A59 A5.99 V (2.61%)224.0 V9.88 V (4.3%)191.7 W✓ OK (≤3%)
25 mm²101 A78 A3.83 V (1.67%)226.2 V6.33 V (2.75%)122.7 W✓ OK (≤3%)
35 mm²125 A97 A2.74 V (1.19%)227.3 V4.52 V (1.96%)87.7 W✓ OK (≤3%)
50 mm²151 A118 A1.92 V (0.83%)228.1 V3.16 V (1.38%)61.4 W✓ OK (≤3%)
70 mm²192 A150 A1.37 V (0.6%)228.6 V2.26 V (0.98%)43.8 W✓ OK (≤3%)
95 mm²232 A181 A1.01 V (0.44%)229.0 V1.66 V (0.72%)32.3 W✓ OK (≤3%)
120 mm²269 A210 A0.8 V (0.35%)229.2 V1.32 V (0.57%)25.6 W✓ OK (≤3%)
150 mm²309 A241 A0.64 V (0.28%)229.4 V1.05 V (0.46%)20.5 W✓ OK (≤3%)
185 mm²353 A275 A0.52 V (0.23%)229.5 V0.85 V (0.37%)16.6 W✓ OK (≤3%)
240 mm²415 A324 A0.4 V (0.17%)229.6 V0.66 V (0.29%)12.8 W✓ OK (≤3%)
300 mm²477 A372 A0.32 V (0.14%)229.7 V0.53 V (0.23%)10.2 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.1%)229.8 V0.4 V (0.17%)7.7 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 32 Ampere ved 70 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 32A over 70 meter (230V)?

Etter NEK 400 anbefales 16 mm² kobberkabel for 32A ved 70 meter (230V), som gir et spenningsfall på 5.99V (2.61%).

Hvor mange kW tåler 32A ved 230V?

Kursen leverer opptil 7.36 kW med 32A vern.