Kabeltverrsnitt for 550 Ampere ved 350 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 550 A over 350 m ved 230V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 6.87V (2.99%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 33.98V (14.77%)
Voltage at Load223.1 VLine Loss: 3776.2 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5492.67 V (2388.12%)0.0 V9060.33 V (3939.28%)3020966.7 WDrop High
2.5 mm²24 A18 A3295.6 V (1432.87%)0.0 V5436.2 V (2363.57%)1812580.0 WDrop High
4 mm²32 A25 A2059.75 V (895.54%)0.0 V3397.62 V (1477.23%)1132862.5 WDrop High
6 mm²41 A32 A1373.17 V (597.03%)0.0 V2265.08 V (984.82%)755241.7 WDrop High
10 mm²57 A44 A823.9 V (358.22%)0.0 V1359.05 V (590.89%)453145.0 WDrop High
16 mm²76 A59 A514.94 V (223.89%)0.0 V849.41 V (369.31%)283215.6 WDrop High
25 mm²101 A78 A329.56 V (143.29%)0.0 V543.62 V (236.36%)181258.0 WDrop High
35 mm²125 A97 A235.4 V (102.35%)0.0 V388.3 V (168.83%)129470.0 WDrop High
50 mm²151 A118 A164.78 V (71.64%)65.2 V271.81 V (118.18%)90629.0 WDrop High
70 mm²192 A150 A117.7 V (51.17%)112.3 V194.15 V (84.41%)64735.0 WDrop High
95 mm²232 A181 A86.73 V (37.71%)143.3 V143.06 V (62.2%)47699.5 WDrop High
120 mm²269 A210 A68.66 V (29.85%)161.3 V113.25 V (49.24%)37762.1 WDrop High
150 mm²309 A241 A54.93 V (23.88%)175.1 V90.6 V (39.39%)30209.7 WDrop High
185 mm²353 A275 A44.54 V (19.36%)185.5 V73.46 V (31.94%)24494.3 WDrop High
240 mm²415 A324 A34.33 V (14.93%)195.7 V56.63 V (24.62%)18881.0 WDrop High
300 mm²477 A372 A27.46 V (11.94%)202.5 V45.3 V (19.7%)15104.8 WDrop High
400 mm²570 A445 A20.6 V (8.96%)209.4 V33.98 V (14.77%)11328.6 WDrop High

FAQ — Kabeltverrsnitt for 550 Ampere ved 350 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 550A over 350 meter (230V)?

Etter NEK 400 anbefales 3× 400 mm² kobberkabel for 550A ved 350 meter (230V), som gir et spenningsfall på 6.87V (2.99%).

Hvor mange kW tåler 550A ved 230V?

Kursen leverer opptil 126.5 kW med 600A vern.