⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 650 Ampere ved 350 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 650 A over 350 m ved 230V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 6.08V (2.65%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 40.15V (17.46%)
Voltage at Load223.9 VLine Loss: 3955.7 W
Max Power & Breaker149.5 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6491.33 V (2822.32%)0.0 V10707.67 V (4655.51%)4219366.7 WDrop High
2.5 mm²24 A18 A3894.8 V (1693.39%)0.0 V6424.6 V (2793.3%)2531620.0 WDrop High
4 mm²32 A25 A2434.25 V (1058.37%)0.0 V4015.37 V (1745.82%)1582262.5 WDrop High
6 mm²41 A32 A1622.83 V (705.58%)0.0 V2676.92 V (1163.88%)1054841.7 WDrop High
10 mm²57 A44 A973.7 V (423.35%)0.0 V1606.15 V (698.33%)632905.0 WDrop High
16 mm²76 A59 A608.56 V (264.59%)0.0 V1003.84 V (436.45%)395565.6 WDrop High
25 mm²101 A78 A389.48 V (169.34%)0.0 V642.46 V (279.33%)253162.0 WDrop High
35 mm²125 A97 A278.2 V (120.96%)0.0 V458.9 V (199.52%)180830.0 WDrop High
50 mm²151 A118 A194.74 V (84.67%)35.3 V321.23 V (139.67%)126581.0 WDrop High
70 mm²192 A150 A139.1 V (60.48%)90.9 V229.45 V (99.76%)90415.0 WDrop High
95 mm²232 A181 A102.49 V (44.56%)127.5 V169.07 V (73.51%)66621.6 WDrop High
120 mm²269 A210 A81.14 V (35.28%)148.9 V133.85 V (58.19%)52742.1 WDrop High
150 mm²309 A241 A64.91 V (28.22%)165.1 V107.08 V (46.56%)42193.7 WDrop High
185 mm²353 A275 A52.63 V (22.88%)177.4 V86.82 V (37.75%)34211.1 WDrop High
240 mm²415 A324 A40.57 V (17.64%)189.4 V66.92 V (29.1%)26371.0 WDrop High
300 mm²477 A372 A32.46 V (14.11%)197.5 V53.54 V (23.28%)21096.8 WDrop High
400 mm²570 A445 A24.34 V (10.58%)205.7 V40.15 V (17.46%)15822.6 WDrop High

FAQ — Kabeltverrsnitt for 650 Ampere ved 350 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 650A over 350 meter (230V)?

Etter NEK 400 anbefales 4× 400 mm² kobberkabel for 650A ved 350 meter (230V), som gir et spenningsfall på 6.08V (2.65%).

Hvor mange kW tåler 650A ved 230V?

Kursen leverer opptil 149.5 kW med 700A vern.