⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 750 Ampere ved 250 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 750 A over 250 m ved 230V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 33.09V (14.39%)
Voltage at Load223.3 VLine Loss: 5015.6 W
Max Power & Breaker172.5 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5350.0 V (2326.09%)0.0 V8825.0 V (3836.96%)4012500.0 WDrop High
2.5 mm²24 A18 A3210.0 V (1395.65%)0.0 V5295.0 V (2302.17%)2407500.0 WDrop High
4 mm²32 A25 A2006.25 V (872.28%)0.0 V3309.37 V (1438.86%)1504687.5 WDrop High
6 mm²41 A32 A1337.5 V (581.52%)0.0 V2206.25 V (959.24%)1003125.0 WDrop High
10 mm²57 A44 A802.5 V (348.91%)0.0 V1323.75 V (575.54%)601875.0 WDrop High
16 mm²76 A59 A501.56 V (218.07%)0.0 V827.34 V (359.71%)376171.9 WDrop High
25 mm²101 A78 A321.0 V (139.57%)0.0 V529.5 V (230.22%)240750.0 WDrop High
35 mm²125 A97 A229.29 V (99.69%)0.7 V378.21 V (164.44%)171964.3 WDrop High
50 mm²151 A118 A160.5 V (69.78%)69.5 V264.75 V (115.11%)120375.0 WDrop High
70 mm²192 A150 A114.64 V (49.84%)115.4 V189.11 V (82.22%)85982.1 WDrop High
95 mm²232 A181 A84.47 V (36.73%)145.5 V139.34 V (60.58%)63355.3 WDrop High
120 mm²269 A210 A66.88 V (29.08%)163.1 V110.31 V (47.96%)50156.2 WDrop High
150 mm²309 A241 A53.5 V (23.26%)176.5 V88.25 V (38.37%)40125.0 WDrop High
185 mm²353 A275 A43.38 V (18.86%)186.6 V71.55 V (31.11%)32533.8 WDrop High
240 mm²415 A324 A33.44 V (14.54%)196.6 V55.16 V (23.98%)25078.1 WDrop High
300 mm²477 A372 A26.75 V (11.63%)203.2 V44.12 V (19.18%)20062.5 WDrop High
400 mm²570 A445 A20.06 V (8.72%)209.9 V33.09 V (14.39%)15046.9 WDrop High

FAQ — Kabeltverrsnitt for 750 Ampere ved 250 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 750A over 250 meter (230V)?

Etter NEK 400 anbefales 3× 400 mm² kobberkabel for 750A ved 250 meter (230V), som gir et spenningsfall på 6.69V (2.91%).

Hvor mange kW tåler 750A ved 230V?

Kursen leverer opptil 172.5 kW med 800A vern.