Kabeltverrsnitt for 16 Ampere ved 250 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 16 A over 250 m ved 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.65V (2.46%)
Voltage at Load223.2 VLine Loss: 109.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A114.13 V (49.62%)115.9 V188.27 V (81.86%)1826.1 WDrop High
2.5 mm²24 A18 A68.48 V (29.77%)161.5 V112.96 V (49.11%)1095.7 WDrop High
4 mm²32 A25 A42.8 V (18.61%)187.2 V70.6 V (30.7%)684.8 WDrop High
6 mm²41 A32 A28.53 V (12.41%)201.5 V47.07 V (20.46%)456.5 WDrop High
10 mm²57 A44 A17.12 V (7.44%)212.9 V28.24 V (12.28%)273.9 WDrop High
16 mm²76 A59 A10.7 V (4.65%)219.3 V17.65 V (7.67%)171.2 W~ ≤5%
25 mm²101 A78 A6.85 V (2.98%)223.2 V11.3 V (4.91%)109.6 W✓ OK (≤3%)
35 mm²125 A97 A4.89 V (2.13%)225.1 V8.07 V (3.51%)78.3 W✓ OK (≤3%)
50 mm²151 A118 A3.42 V (1.49%)226.6 V5.65 V (2.46%)54.8 W✓ OK (≤3%)
70 mm²192 A150 A2.45 V (1.06%)227.6 V4.03 V (1.75%)39.1 W✓ OK (≤3%)
95 mm²232 A181 A1.8 V (0.78%)228.2 V2.97 V (1.29%)28.8 W✓ OK (≤3%)
120 mm²269 A210 A1.43 V (0.62%)228.6 V2.35 V (1.02%)22.8 W✓ OK (≤3%)
150 mm²309 A241 A1.14 V (0.5%)228.9 V1.88 V (0.82%)18.3 W✓ OK (≤3%)
185 mm²353 A275 A0.93 V (0.4%)229.1 V1.53 V (0.66%)14.8 W✓ OK (≤3%)
240 mm²415 A324 A0.71 V (0.31%)229.3 V1.18 V (0.51%)11.4 W✓ OK (≤3%)
300 mm²477 A372 A0.57 V (0.25%)229.4 V0.94 V (0.41%)9.1 W✓ OK (≤3%)
400 mm²570 A445 A0.43 V (0.19%)229.6 V0.71 V (0.31%)6.8 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 16 Ampere ved 250 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 16A over 250 meter (230V)?

Etter NEK 400 anbefales 25 mm² kobberkabel for 16A ved 250 meter (230V), som gir et spenningsfall på 6.85V (2.98%).

Hvor mange kW tåler 16A ved 230V?

Kursen leverer opptil 3.68 kW med 16A vern.