Kabeltverrsnitt for 90 Ampere ved 5 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 90 A over 5 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 0.67V (0.17%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 0.79V (0.2%)
Voltage at Load399.3 VLine Loss: 104.0 W
Max Power & Breaker62.35 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.12 V (2.78%)388.9 V18.34 V (4.59%)1733.4 WDrop High
2.5 mm²24 A18 A6.67 V (1.67%)393.3 V11.01 V (2.75%)1040.0 WDrop High
4 mm²32 A25 A4.17 V (1.04%)395.8 V6.88 V (1.72%)650.0 WDrop High
6 mm²41 A32 A2.78 V (0.69%)397.2 V4.59 V (1.15%)433.3 WDrop High
10 mm²57 A44 A1.67 V (0.42%)398.3 V2.75 V (0.69%)260.0 WDrop High
16 mm²76 A59 A1.04 V (0.26%)399.0 V1.72 V (0.43%)162.5 WDrop High
25 mm²101 A78 A0.67 V (0.17%)399.3 V1.1 V (0.28%)104.0 W✓ OK (≤3%)
35 mm²125 A97 A0.48 V (0.12%)399.5 V0.79 V (0.2%)74.3 W✓ OK (≤3%)
50 mm²151 A118 A0.33 V (0.08%)399.7 V0.55 V (0.14%)52.0 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.06%)399.8 V0.39 V (0.1%)37.1 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.04%)399.8 V0.29 V (0.07%)27.4 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.03%)399.9 V0.23 V (0.06%)21.7 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.03%)399.9 V0.18 V (0.05%)17.3 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.02%)399.9 V0.15 V (0.04%)14.1 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.02%)399.9 V0.11 V (0.03%)10.8 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)399.9 V0.09 V (0.02%)8.7 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)400.0 V0.07 V (0.02%)6.5 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 90 Ampere ved 5 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 90A over 5 meter (400V)?

Etter NEK 400 anbefales 25 mm² kobberkabel for 90A ved 5 meter (400V), som gir et spenningsfall på 0.67V (0.17%).

Hvor mange kW tåler 90A ved 400V?

Kursen leverer opptil 62.35 kW med 90A vern.