Kabelarea för 10 Ampere vid 80 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 10 A över 80 m vid 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 8.15V (2.04%)
Voltage at Load388.1 VLine Loss: 205.4 W
Max Power & Breaker6.93 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.77 V (4.94%)380.2 V32.61 V (8.15%)342.4 W~ ≤5%
2.5 mm²24 A18 A11.86 V (2.97%)388.1 V19.57 V (4.89%)205.4 W✓ OK (≤3%)
4 mm²32 A25 A7.41 V (1.85%)392.6 V12.23 V (3.06%)128.4 W✓ OK (≤3%)
6 mm²41 A32 A4.94 V (1.24%)395.1 V8.15 V (2.04%)85.6 W✓ OK (≤3%)
10 mm²57 A44 A2.97 V (0.74%)397.0 V4.89 V (1.22%)51.4 W✓ OK (≤3%)
16 mm²76 A59 A1.85 V (0.46%)398.1 V3.06 V (0.76%)32.1 W✓ OK (≤3%)
25 mm²101 A78 A1.19 V (0.3%)398.8 V1.96 V (0.49%)20.5 W✓ OK (≤3%)
35 mm²125 A97 A0.85 V (0.21%)399.2 V1.4 V (0.35%)14.7 W✓ OK (≤3%)
50 mm²151 A118 A0.59 V (0.15%)399.4 V0.98 V (0.24%)10.3 W✓ OK (≤3%)
70 mm²192 A150 A0.42 V (0.11%)399.6 V0.7 V (0.17%)7.3 W✓ OK (≤3%)
95 mm²232 A181 A0.31 V (0.08%)399.7 V0.51 V (0.13%)5.4 W✓ OK (≤3%)
120 mm²269 A210 A0.25 V (0.06%)399.8 V0.41 V (0.1%)4.3 W✓ OK (≤3%)
150 mm²309 A241 A0.2 V (0.05%)399.8 V0.33 V (0.08%)3.4 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.04%)399.8 V0.26 V (0.07%)2.8 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.03%)399.9 V0.2 V (0.05%)2.1 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.02%)399.9 V0.16 V (0.04%)1.7 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.02%)399.9 V0.12 V (0.03%)1.3 W✓ OK (≤3%)

FAQ — Kabelarea för 10 Ampere vid 80 Meter (400V)

Vilken kabelarea krävs för 10A vid 80 meter (400V)?

För 10 Ampere över 80 meter vid 400V rekommenderas 2.5 mm² kopparkabel för att hålla spänningsfallet under 3% (11.86V / 2.97%).

Hur stor effekt motsvarar 10A vid 400V?

Det motsvarar 6.93 kW med en rekommenderad säkring på 10A.