⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 160 Ampere vid 80 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 80 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 6.78V (1.69%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 8.24V (2.06%)
Voltage at Load393.2 VLine Loss: 1878.3 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A316.3 V (79.07%)83.7 V521.74 V (130.43%)87654.4 WDrop High
2.5 mm²24 A18 A189.78 V (47.44%)210.2 V313.04 V (78.26%)52592.6 WDrop High
4 mm²32 A25 A118.61 V (29.65%)281.4 V195.65 V (48.91%)32870.4 WDrop High
6 mm²41 A32 A79.07 V (19.77%)320.9 V130.43 V (32.61%)21913.6 WDrop High
10 mm²57 A44 A47.44 V (11.86%)352.6 V78.26 V (19.57%)13148.2 WDrop High
16 mm²76 A59 A29.65 V (7.41%)370.3 V48.91 V (12.23%)8217.6 WDrop High
25 mm²101 A78 A18.98 V (4.74%)381.0 V31.3 V (7.83%)5259.3 WDrop High
35 mm²125 A97 A13.56 V (3.39%)386.4 V22.36 V (5.59%)3756.6 WDrop High
50 mm²151 A118 A9.49 V (2.37%)390.5 V15.65 V (3.91%)2629.6 WDrop High
70 mm²192 A150 A6.78 V (1.69%)393.2 V11.18 V (2.8%)1878.3 W✓ OK (≤3%)
95 mm²232 A181 A4.99 V (1.25%)395.0 V8.24 V (2.06%)1384.0 W✓ OK (≤3%)
120 mm²269 A210 A3.95 V (0.99%)396.0 V6.52 V (1.63%)1095.7 W✓ OK (≤3%)
150 mm²309 A241 A3.16 V (0.79%)396.8 V5.22 V (1.3%)876.5 W✓ OK (≤3%)
185 mm²353 A275 A2.56 V (0.64%)397.4 V4.23 V (1.06%)710.7 W✓ OK (≤3%)
240 mm²415 A324 A1.98 V (0.49%)398.0 V3.26 V (0.82%)547.8 W✓ OK (≤3%)
300 mm²477 A372 A1.58 V (0.4%)398.4 V2.61 V (0.65%)438.3 W✓ OK (≤3%)
400 mm²570 A445 A1.19 V (0.3%)398.8 V1.96 V (0.49%)328.7 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 80 Meter (400V)

Vilken kabelarea krävs för 160A vid 80 meter (400V)?

För 160 Ampere över 80 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (6.78V / 1.69%).

Hur stor effekt motsvarar 160A vid 400V?

Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.