Kabelarea för 100 Ampere vid 50 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 100 A över 50 m vid 400V.
Copper Cable (≤3% Drop)25 mm²Drop: 7.41V (1.85%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 6.11V (1.53%)
Voltage at Load392.6 VLine Loss: 1284.0 W
Max Power & Breaker69.28 kW100A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 50m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 123.55 V (30.89%) | 276.4 V | 203.8 V (50.95%) | 21400.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 74.13 V (18.53%) | 325.9 V | 122.28 V (30.57%) | 12840.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 46.33 V (11.58%) | 353.7 V | 76.43 V (19.11%) | 8025.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 30.89 V (7.72%) | 369.1 V | 50.95 V (12.74%) | 5350.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 3210.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 11.58 V (2.9%) | 388.4 V | 19.11 V (4.78%) | 2006.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 7.41 V (1.85%) | 392.6 V | 12.23 V (3.06%) | 1284.0 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 5.3 V (1.32%) | 394.7 V | 8.73 V (2.18%) | 917.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.71 V (0.93%) | 396.3 V | 6.11 V (1.53%) | 642.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.65 V (0.66%) | 397.4 V | 4.37 V (1.09%) | 458.6 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.95 V (0.49%) | 398.0 V | 3.22 V (0.8%) | 337.9 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.54 V (0.39%) | 398.5 V | 2.55 V (0.64%) | 267.5 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.24 V (0.31%) | 398.8 V | 2.04 V (0.51%) | 214.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.0 V (0.25%) | 399.0 V | 1.65 V (0.41%) | 173.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.77 V (0.19%) | 399.2 V | 1.27 V (0.32%) | 133.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.62 V (0.15%) | 399.4 V | 1.02 V (0.25%) | 107.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.46 V (0.12%) | 399.5 V | 0.76 V (0.19%) | 80.2 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 100 Ampere vid 50 Meter (400V)
Vilken kabelarea krävs för 100A vid 50 meter (400V)?
För 100 Ampere över 50 meter vid 400V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (7.41V / 1.85%).
Hur stor effekt motsvarar 100A vid 400V?
Det motsvarar 69.28 kW med en rekommenderad säkring på 100A.
Related Lengths & Currents (400V)
100A · 5m (400V)100A · 10m (400V)100A · 15m (400V)100A · 20m (400V)100A · 25m (400V)100A · 30m (400V)100A · 35m (400V)100A · 40m (400V)100A · 45m (400V)100A · 60m (400V)100A · 70m (400V)10A · 50m (400V)16A · 50m (400V)20A · 50m (400V)25A · 50m (400V)32A · 50m (400V)40A · 50m (400V)50A · 50m (400V)63A · 50m (400V)80A · 50m (400V)125A · 50m (400V)160A · 50m (400V)200A · 50m (400V)