Kabelarea för 20 Ampere vid 50 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 20 A över 50 m vid 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 10.19V (2.55%)
Voltage at Load390.7 VLine Loss: 321.0 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.71 V (6.18%)375.3 V40.76 V (10.19%)856.0 WDrop High
2.5 mm²24 A18 A14.83 V (3.71%)385.2 V24.46 V (6.11%)513.6 W~ ≤5%
4 mm²32 A25 A9.27 V (2.32%)390.7 V15.29 V (3.82%)321.0 W✓ OK (≤3%)
6 mm²41 A32 A6.18 V (1.54%)393.8 V10.19 V (2.55%)214.0 W✓ OK (≤3%)
10 mm²57 A44 A3.71 V (0.93%)396.3 V6.11 V (1.53%)128.4 W✓ OK (≤3%)
16 mm²76 A59 A2.32 V (0.58%)397.7 V3.82 V (0.96%)80.2 W✓ OK (≤3%)
25 mm²101 A78 A1.48 V (0.37%)398.5 V2.45 V (0.61%)51.4 W✓ OK (≤3%)
35 mm²125 A97 A1.06 V (0.26%)398.9 V1.75 V (0.44%)36.7 W✓ OK (≤3%)
50 mm²151 A118 A0.74 V (0.19%)399.3 V1.22 V (0.31%)25.7 W✓ OK (≤3%)
70 mm²192 A150 A0.53 V (0.13%)399.5 V0.87 V (0.22%)18.3 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (0.1%)399.6 V0.64 V (0.16%)13.5 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (0.08%)399.7 V0.51 V (0.13%)10.7 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (0.06%)399.8 V0.41 V (0.1%)8.6 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.05%)399.8 V0.33 V (0.08%)6.9 W✓ OK (≤3%)
240 mm²415 A324 A0.15 V (0.04%)399.8 V0.25 V (0.06%)5.3 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.03%)399.9 V0.2 V (0.05%)4.3 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.02%)399.9 V0.15 V (0.04%)3.2 W✓ OK (≤3%)

FAQ — Kabelarea för 20 Ampere vid 50 Meter (400V)

Vilken kabelarea krävs för 20A vid 50 meter (400V)?

För 20 Ampere över 50 meter vid 400V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).

Hur stor effekt motsvarar 20A vid 400V?

Det motsvarar 13.86 kW med en rekommenderad säkring på 20A.