Kabelarea för 1000 Ampere vid 150 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 1000 A över 150 m vid 230V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 26.47V (11.51%)
Voltage at Load224.7 VLine Loss: 5350.0 W
Max Power & Breaker230.0 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4280.0 V (1860.87%)0.0 V7060.0 V (3069.57%)4280000.0 WDrop High
2.5 mm²24 A18 A2568.0 V (1116.52%)0.0 V4236.0 V (1841.74%)2568000.0 WDrop High
4 mm²32 A25 A1605.0 V (697.83%)0.0 V2647.5 V (1151.09%)1605000.0 WDrop High
6 mm²41 A32 A1070.0 V (465.22%)0.0 V1765.0 V (767.39%)1070000.0 WDrop High
10 mm²57 A44 A642.0 V (279.13%)0.0 V1059.0 V (460.43%)642000.0 WDrop High
16 mm²76 A59 A401.25 V (174.46%)0.0 V661.88 V (287.77%)401250.0 WDrop High
25 mm²101 A78 A256.8 V (111.65%)0.0 V423.6 V (184.17%)256800.0 WDrop High
35 mm²125 A97 A183.43 V (79.75%)46.6 V302.57 V (131.55%)183428.6 WDrop High
50 mm²151 A118 A128.4 V (55.83%)101.6 V211.8 V (92.09%)128400.0 WDrop High
70 mm²192 A150 A91.71 V (39.88%)138.3 V151.29 V (65.78%)91714.3 WDrop High
95 mm²232 A181 A67.58 V (29.38%)162.4 V111.47 V (48.47%)67578.9 WDrop High
120 mm²269 A210 A53.5 V (23.26%)176.5 V88.25 V (38.37%)53500.0 WDrop High
150 mm²309 A241 A42.8 V (18.61%)187.2 V70.6 V (30.7%)42800.0 WDrop High
185 mm²353 A275 A34.7 V (15.09%)195.3 V57.24 V (24.89%)34702.7 WDrop High
240 mm²415 A324 A26.75 V (11.63%)203.2 V44.12 V (19.18%)26750.0 WDrop High
300 mm²477 A372 A21.4 V (9.3%)208.6 V35.3 V (15.35%)21400.0 WDrop High
400 mm²570 A445 A16.05 V (6.98%)213.9 V26.47 V (11.51%)16050.0 WDrop High

FAQ — Kabelarea för 1000 Ampere vid 150 Meter (230V)

Vilken kabelarea krävs för 1000A vid 150 meter (230V)?

För 1000 Ampere över 150 meter vid 230V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.35V / 2.33%).

Hur stor effekt motsvarar 1000A vid 230V?

Det motsvarar 230.0 kW med en rekommenderad säkring på 1000A.