⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 1000 Ampere vid 25 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 1000 A över 25 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.16V (0.29%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.82V (0.96%)
Voltage at Load398.8 VLine Loss: 2006.2 W
Max Power & Breaker692.82 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A617.76 V (154.44%)0.0 V1019.02 V (254.76%)1070000.0 WDrop High
2.5 mm²24 A18 A370.66 V (92.66%)29.3 V611.41 V (152.85%)642000.0 WDrop High
4 mm²32 A25 A231.66 V (57.92%)168.3 V382.13 V (95.53%)401250.0 WDrop High
6 mm²41 A32 A154.44 V (38.61%)245.6 V254.76 V (63.69%)267500.0 WDrop High
10 mm²57 A44 A92.66 V (23.17%)307.3 V152.85 V (38.21%)160500.0 WDrop High
16 mm²76 A59 A57.92 V (14.48%)342.1 V95.53 V (23.88%)100312.5 WDrop High
25 mm²101 A78 A37.07 V (9.27%)362.9 V61.14 V (15.29%)64200.0 WDrop High
35 mm²125 A97 A26.48 V (6.62%)373.5 V43.67 V (10.92%)45857.1 WDrop High
50 mm²151 A118 A18.53 V (4.63%)381.5 V30.57 V (7.64%)32100.0 WDrop High
70 mm²192 A150 A13.24 V (3.31%)386.8 V21.84 V (5.46%)22928.6 WDrop High
95 mm²232 A181 A9.75 V (2.44%)390.2 V16.09 V (4.02%)16894.7 WDrop High
120 mm²269 A210 A7.72 V (1.93%)392.3 V12.74 V (3.18%)13375.0 WDrop High
150 mm²309 A241 A6.18 V (1.54%)393.8 V10.19 V (2.55%)10700.0 WDrop High
185 mm²353 A275 A5.01 V (1.25%)395.0 V8.26 V (2.07%)8675.7 WDrop High
240 mm²415 A324 A3.86 V (0.97%)396.1 V6.37 V (1.59%)6687.5 WDrop High
300 mm²477 A372 A3.09 V (0.77%)396.9 V5.1 V (1.27%)5350.0 WDrop High
400 mm²570 A445 A2.32 V (0.58%)397.7 V3.82 V (0.96%)4012.5 WDrop High

FAQ — Kabelarea för 1000 Ampere vid 25 Meter (400V)

Vilken kabelarea krävs för 1000A vid 25 meter (400V)?

För 1000 Ampere över 25 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.16V / 0.29%).

Hur stor effekt motsvarar 1000A vid 400V?

Det motsvarar 692.82 kW med en rekommenderad säkring på 1000A.