⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 160 Ampere vid 25 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 25 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 2.12V (0.53%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 2.57V (0.64%)
Voltage at Load397.9 VLine Loss: 587.0 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A98.84 V (24.71%)301.2 V163.04 V (40.76%)27392.0 WDrop High
2.5 mm²24 A18 A59.31 V (14.83%)340.7 V97.83 V (24.46%)16435.2 WDrop High
4 mm²32 A25 A37.07 V (9.27%)362.9 V61.14 V (15.29%)10272.0 WDrop High
6 mm²41 A32 A24.71 V (6.18%)375.3 V40.76 V (10.19%)6848.0 WDrop High
10 mm²57 A44 A14.83 V (3.71%)385.2 V24.46 V (6.11%)4108.8 WDrop High
16 mm²76 A59 A9.27 V (2.32%)390.7 V15.29 V (3.82%)2568.0 WDrop High
25 mm²101 A78 A5.93 V (1.48%)394.1 V9.78 V (2.45%)1643.5 WDrop High
35 mm²125 A97 A4.24 V (1.06%)395.8 V6.99 V (1.75%)1173.9 WDrop High
50 mm²151 A118 A2.97 V (0.74%)397.0 V4.89 V (1.22%)821.8 WDrop High
70 mm²192 A150 A2.12 V (0.53%)397.9 V3.49 V (0.87%)587.0 W✓ OK (≤3%)
95 mm²232 A181 A1.56 V (0.39%)398.4 V2.57 V (0.64%)432.5 W✓ OK (≤3%)
120 mm²269 A210 A1.24 V (0.31%)398.8 V2.04 V (0.51%)342.4 W✓ OK (≤3%)
150 mm²309 A241 A0.99 V (0.25%)399.0 V1.63 V (0.41%)273.9 W✓ OK (≤3%)
185 mm²353 A275 A0.8 V (0.2%)399.2 V1.32 V (0.33%)222.1 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (0.15%)399.4 V1.02 V (0.25%)171.2 W✓ OK (≤3%)
300 mm²477 A372 A0.49 V (0.12%)399.5 V0.82 V (0.2%)137.0 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.09%)399.6 V0.61 V (0.15%)102.7 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 25 Meter (400V)

Vilken kabelarea krävs för 160A vid 25 meter (400V)?

För 160 Ampere över 25 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (2.12V / 0.53%).

Hur stor effekt motsvarar 160A vid 400V?

Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.