Kabelarea för 225 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 225 A över 45 m vid 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 4.56V (1.98%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 4.77V (2.07%)
Voltage at Load225.4 VLine Loss: 1026.4 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A288.9 V (125.61%)0.0 V476.55 V (207.2%)65002.5 WDrop High
2.5 mm²24 A18 A173.34 V (75.37%)56.7 V285.93 V (124.32%)39001.5 WDrop High
4 mm²32 A25 A108.34 V (47.1%)121.7 V178.71 V (77.7%)24375.9 WDrop High
6 mm²41 A32 A72.23 V (31.4%)157.8 V119.14 V (51.8%)16250.6 WDrop High
10 mm²57 A44 A43.34 V (18.84%)186.7 V71.48 V (31.08%)9750.4 WDrop High
16 mm²76 A59 A27.08 V (11.78%)202.9 V44.68 V (19.42%)6094.0 WDrop High
25 mm²101 A78 A17.33 V (7.54%)212.7 V28.59 V (12.43%)3900.2 WDrop High
35 mm²125 A97 A12.38 V (5.38%)217.6 V20.42 V (8.88%)2785.8 WDrop High
50 mm²151 A118 A8.67 V (3.77%)221.3 V14.3 V (6.22%)1950.1 WDrop High
70 mm²192 A150 A6.19 V (2.69%)223.8 V10.21 V (4.44%)1392.9 WDrop High
95 mm²232 A181 A4.56 V (1.98%)225.4 V7.52 V (3.27%)1026.4 W✓ OK (≤3%)
120 mm²269 A210 A3.61 V (1.57%)226.4 V5.96 V (2.59%)812.5 W✓ OK (≤3%)
150 mm²309 A241 A2.89 V (1.26%)227.1 V4.77 V (2.07%)650.0 W✓ OK (≤3%)
185 mm²353 A275 A2.34 V (1.02%)227.7 V3.86 V (1.68%)527.0 W✓ OK (≤3%)
240 mm²415 A324 A1.81 V (0.79%)228.2 V2.98 V (1.29%)406.3 W✓ OK (≤3%)
300 mm²477 A372 A1.44 V (0.63%)228.6 V2.38 V (1.04%)325.0 W✓ OK (≤3%)
400 mm²570 A445 A1.08 V (0.47%)228.9 V1.79 V (0.78%)243.8 W✓ OK (≤3%)

FAQ — Kabelarea för 225 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 225A vid 45 meter (230V)?

För 225 Ampere över 45 meter vid 230V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (4.56V / 1.98%).

Hur stor effekt motsvarar 225A vid 230V?

Det motsvarar 51.75 kW med en rekommenderad säkring på 225A.