Kabelarea för 225 Ampere vid 15 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 225 A över 15 m vid 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 1.52V (0.66%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 1.59V (0.69%)
Voltage at Load228.5 VLine Loss: 342.1 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A96.3 V (41.87%)133.7 V158.85 V (69.07%)21667.5 WDrop High
2.5 mm²24 A18 A57.78 V (25.12%)172.2 V95.31 V (41.44%)13000.5 WDrop High
4 mm²32 A25 A36.11 V (15.7%)193.9 V59.57 V (25.9%)8125.3 WDrop High
6 mm²41 A32 A24.07 V (10.47%)205.9 V39.71 V (17.27%)5416.9 WDrop High
10 mm²57 A44 A14.45 V (6.28%)215.6 V23.83 V (10.36%)3250.1 WDrop High
16 mm²76 A59 A9.03 V (3.93%)221.0 V14.89 V (6.47%)2031.3 WDrop High
25 mm²101 A78 A5.78 V (2.51%)224.2 V9.53 V (4.14%)1300.1 WDrop High
35 mm²125 A97 A4.13 V (1.79%)225.9 V6.81 V (2.96%)928.6 WDrop High
50 mm²151 A118 A2.89 V (1.26%)227.1 V4.77 V (2.07%)650.0 WDrop High
70 mm²192 A150 A2.06 V (0.9%)227.9 V3.4 V (1.48%)464.3 WDrop High
95 mm²232 A181 A1.52 V (0.66%)228.5 V2.51 V (1.09%)342.1 W✓ OK (≤3%)
120 mm²269 A210 A1.2 V (0.52%)228.8 V1.99 V (0.86%)270.8 W✓ OK (≤3%)
150 mm²309 A241 A0.96 V (0.42%)229.0 V1.59 V (0.69%)216.7 W✓ OK (≤3%)
185 mm²353 A275 A0.78 V (0.34%)229.2 V1.29 V (0.56%)175.7 W✓ OK (≤3%)
240 mm²415 A324 A0.6 V (0.26%)229.4 V0.99 V (0.43%)135.4 W✓ OK (≤3%)
300 mm²477 A372 A0.48 V (0.21%)229.5 V0.79 V (0.35%)108.3 W✓ OK (≤3%)
400 mm²570 A445 A0.36 V (0.16%)229.6 V0.6 V (0.26%)81.3 W✓ OK (≤3%)

FAQ — Kabelarea för 225 Ampere vid 15 Meter (230V)

Vilken kabelarea krävs för 225A vid 15 meter (230V)?

För 225 Ampere över 15 meter vid 230V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (1.52V / 0.66%).

Hur stor effekt motsvarar 225A vid 230V?

Det motsvarar 51.75 kW med en rekommenderad säkring på 225A.