⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 25 Ampere vid 175 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 25 A över 175 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 6.18V (2.69%)
Voltage at Load224.7 VLine Loss: 133.7 W
Max Power & Breaker5.75 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A124.83 V (54.28%)105.2 V205.92 V (89.53%)3120.8 WDrop High
2.5 mm²24 A18 A74.9 V (32.57%)155.1 V123.55 V (53.72%)1872.5 WDrop High
4 mm²32 A25 A46.81 V (20.35%)183.2 V77.22 V (33.57%)1170.3 WDrop High
6 mm²41 A32 A31.21 V (13.57%)198.8 V51.48 V (22.38%)780.2 WDrop High
10 mm²57 A44 A18.72 V (8.14%)211.3 V30.89 V (13.43%)468.1 WDrop High
16 mm²76 A59 A11.7 V (5.09%)218.3 V19.3 V (8.39%)292.6 WDrop High
25 mm²101 A78 A7.49 V (3.26%)222.5 V12.35 V (5.37%)187.2 W~ ≤5%
35 mm²125 A97 A5.35 V (2.33%)224.7 V8.82 V (3.84%)133.7 W✓ OK (≤3%)
50 mm²151 A118 A3.74 V (1.63%)226.3 V6.18 V (2.69%)93.6 W✓ OK (≤3%)
70 mm²192 A150 A2.67 V (1.16%)227.3 V4.41 V (1.92%)66.9 W✓ OK (≤3%)
95 mm²232 A181 A1.97 V (0.86%)228.0 V3.25 V (1.41%)49.3 W✓ OK (≤3%)
120 mm²269 A210 A1.56 V (0.68%)228.4 V2.57 V (1.12%)39.0 W✓ OK (≤3%)
150 mm²309 A241 A1.25 V (0.54%)228.8 V2.06 V (0.9%)31.2 W✓ OK (≤3%)
185 mm²353 A275 A1.01 V (0.44%)229.0 V1.67 V (0.73%)25.3 W✓ OK (≤3%)
240 mm²415 A324 A0.78 V (0.34%)229.2 V1.29 V (0.56%)19.5 W✓ OK (≤3%)
300 mm²477 A372 A0.62 V (0.27%)229.4 V1.03 V (0.45%)15.6 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.2%)229.5 V0.77 V (0.34%)11.7 W✓ OK (≤3%)

FAQ — Kabelarea för 25 Ampere vid 175 Meter (230V)

Vilken kabelarea krävs för 25A vid 175 meter (230V)?

För 25 Ampere över 175 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (5.35V / 2.33%).

Hur stor effekt motsvarar 25A vid 230V?

Det motsvarar 5.75 kW med en rekommenderad säkring på 25A.