Kabelarea för 40 Ampere vid 175 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 40 A över 175 m vid 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 5.2V (2.26%)
Voltage at Load224.0 VLine Loss: 239.7 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A199.73 V (86.84%)30.3 V329.47 V (143.25%)7989.3 WDrop High
2.5 mm²24 A18 A119.84 V (52.1%)110.2 V197.68 V (85.95%)4793.6 WDrop High
4 mm²32 A25 A74.9 V (32.57%)155.1 V123.55 V (53.72%)2996.0 WDrop High
6 mm²41 A32 A49.93 V (21.71%)180.1 V82.37 V (35.81%)1997.3 WDrop High
10 mm²57 A44 A29.96 V (13.03%)200.0 V49.42 V (21.49%)1198.4 WDrop High
16 mm²76 A59 A18.72 V (8.14%)211.3 V30.89 V (13.43%)749.0 WDrop High
25 mm²101 A78 A11.98 V (5.21%)218.0 V19.77 V (8.59%)479.4 WDrop High
35 mm²125 A97 A8.56 V (3.72%)221.4 V14.12 V (6.14%)342.4 W~ ≤5%
50 mm²151 A118 A5.99 V (2.61%)224.0 V9.88 V (4.3%)239.7 W✓ OK (≤3%)
70 mm²192 A150 A4.28 V (1.86%)225.7 V7.06 V (3.07%)171.2 W✓ OK (≤3%)
95 mm²232 A181 A3.15 V (1.37%)226.8 V5.2 V (2.26%)126.1 W✓ OK (≤3%)
120 mm²269 A210 A2.5 V (1.09%)227.5 V4.12 V (1.79%)99.9 W✓ OK (≤3%)
150 mm²309 A241 A2.0 V (0.87%)228.0 V3.29 V (1.43%)79.9 W✓ OK (≤3%)
185 mm²353 A275 A1.62 V (0.7%)228.4 V2.67 V (1.16%)64.8 W✓ OK (≤3%)
240 mm²415 A324 A1.25 V (0.54%)228.8 V2.06 V (0.9%)49.9 W✓ OK (≤3%)
300 mm²477 A372 A1.0 V (0.43%)229.0 V1.65 V (0.72%)39.9 W✓ OK (≤3%)
400 mm²570 A445 A0.75 V (0.33%)229.3 V1.24 V (0.54%)30.0 W✓ OK (≤3%)

FAQ — Kabelarea för 40 Ampere vid 175 Meter (230V)

Vilken kabelarea krävs för 40A vid 175 meter (230V)?

För 40 Ampere över 175 meter vid 230V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (5.99V / 2.61%).

Hur stor effekt motsvarar 40A vid 230V?

Det motsvarar 9.2 kW med en rekommenderad säkring på 40A.