Kabelarea för 250 Ampere vid 25 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 250 A över 25 m vid 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 1.93V (0.48%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 2.07V (0.52%)
Voltage at Load398.1 VLine Loss: 835.9 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A154.44 V (38.61%)245.6 V254.76 V (63.69%)66875.0 WDrop High
2.5 mm²24 A18 A92.66 V (23.17%)307.3 V152.85 V (38.21%)40125.0 WDrop High
4 mm²32 A25 A57.92 V (14.48%)342.1 V95.53 V (23.88%)25078.1 WDrop High
6 mm²41 A32 A38.61 V (9.65%)361.4 V63.69 V (15.92%)16718.8 WDrop High
10 mm²57 A44 A23.17 V (5.79%)376.8 V38.21 V (9.55%)10031.2 WDrop High
16 mm²76 A59 A14.48 V (3.62%)385.5 V23.88 V (5.97%)6269.5 WDrop High
25 mm²101 A78 A9.27 V (2.32%)390.7 V15.29 V (3.82%)4012.5 WDrop High
35 mm²125 A97 A6.62 V (1.65%)393.4 V10.92 V (2.73%)2866.1 WDrop High
50 mm²151 A118 A4.63 V (1.16%)395.4 V7.64 V (1.91%)2006.2 WDrop High
70 mm²192 A150 A3.31 V (0.83%)396.7 V5.46 V (1.36%)1433.0 WDrop High
95 mm²232 A181 A2.44 V (0.61%)397.6 V4.02 V (1.01%)1055.9 WDrop High
120 mm²269 A210 A1.93 V (0.48%)398.1 V3.18 V (0.8%)835.9 W✓ OK (≤3%)
150 mm²309 A241 A1.54 V (0.39%)398.5 V2.55 V (0.64%)668.7 W✓ OK (≤3%)
185 mm²353 A275 A1.25 V (0.31%)398.7 V2.07 V (0.52%)542.2 W✓ OK (≤3%)
240 mm²415 A324 A0.97 V (0.24%)399.0 V1.59 V (0.4%)418.0 W✓ OK (≤3%)
300 mm²477 A372 A0.77 V (0.19%)399.2 V1.27 V (0.32%)334.4 W✓ OK (≤3%)
400 mm²570 A445 A0.58 V (0.14%)399.4 V0.96 V (0.24%)250.8 W✓ OK (≤3%)

FAQ — Kabelarea för 250 Ampere vid 25 Meter (400V)

Vilken kabelarea krävs för 250A vid 25 meter (400V)?

För 250 Ampere över 25 meter vid 400V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (1.93V / 0.48%).

Hur stor effekt motsvarar 250A vid 400V?

Det motsvarar 173.21 kW med en rekommenderad säkring på 250A.