⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 250 Ampere vid 500 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 250 A över 500 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.06V (9.59%)
Voltage at Load223.3 VLine Loss: 1671.9 W
Max Power & Breaker57.5 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3566.67 V (1550.72%)0.0 V5883.33 V (2557.97%)891666.7 WDrop High
2.5 mm²24 A18 A2140.0 V (930.43%)0.0 V3530.0 V (1534.78%)535000.0 WDrop High
4 mm²32 A25 A1337.5 V (581.52%)0.0 V2206.25 V (959.24%)334375.0 WDrop High
6 mm²41 A32 A891.67 V (387.68%)0.0 V1470.83 V (639.49%)222916.7 WDrop High
10 mm²57 A44 A535.0 V (232.61%)0.0 V882.5 V (383.7%)133750.0 WDrop High
16 mm²76 A59 A334.38 V (145.38%)0.0 V551.56 V (239.81%)83593.8 WDrop High
25 mm²101 A78 A214.0 V (93.04%)16.0 V353.0 V (153.48%)53500.0 WDrop High
35 mm²125 A97 A152.86 V (66.46%)77.1 V252.14 V (109.63%)38214.3 WDrop High
50 mm²151 A118 A107.0 V (46.52%)123.0 V176.5 V (76.74%)26750.0 WDrop High
70 mm²192 A150 A76.43 V (33.23%)153.6 V126.07 V (54.81%)19107.1 WDrop High
95 mm²232 A181 A56.32 V (24.49%)173.7 V92.89 V (40.39%)14078.9 WDrop High
120 mm²269 A210 A44.58 V (19.38%)185.4 V73.54 V (31.97%)11145.8 WDrop High
150 mm²309 A241 A35.67 V (15.51%)194.3 V58.83 V (25.58%)8916.7 WDrop High
185 mm²353 A275 A28.92 V (12.57%)201.1 V47.7 V (20.74%)7229.7 WDrop High
240 mm²415 A324 A22.29 V (9.69%)207.7 V36.77 V (15.99%)5572.9 WDrop High
300 mm²477 A372 A17.83 V (7.75%)212.2 V29.42 V (12.79%)4458.3 WDrop High
400 mm²570 A445 A13.38 V (5.82%)216.6 V22.06 V (9.59%)3343.8 WDrop High

FAQ — Kabelarea för 250 Ampere vid 500 Meter (230V)

Vilken kabelarea krävs för 250A vid 500 meter (230V)?

För 250 Ampere över 500 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.69V / 2.91%).

Hur stor effekt motsvarar 250A vid 230V?

Det motsvarar 57.5 kW med en rekommenderad säkring på 250A.