⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 30 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 30 A över 45 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.78V (2.51%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.96V (2.59%)
Voltage at Load224.2 VLine Loss: 173.3 W
Max Power & Breaker6.9 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A38.52 V (16.75%)191.5 V63.54 V (27.63%)1155.6 WDrop High
2.5 mm²24 A18 A23.11 V (10.05%)206.9 V38.12 V (16.58%)693.4 WDrop High
4 mm²32 A25 A14.45 V (6.28%)215.6 V23.83 V (10.36%)433.3 WDrop High
6 mm²41 A32 A9.63 V (4.19%)220.4 V15.88 V (6.91%)288.9 W~ ≤5%
10 mm²57 A44 A5.78 V (2.51%)224.2 V9.53 V (4.14%)173.3 W✓ OK (≤3%)
16 mm²76 A59 A3.61 V (1.57%)226.4 V5.96 V (2.59%)108.3 W✓ OK (≤3%)
25 mm²101 A78 A2.31 V (1.0%)227.7 V3.81 V (1.66%)69.3 W✓ OK (≤3%)
35 mm²125 A97 A1.65 V (0.72%)228.3 V2.72 V (1.18%)49.5 W✓ OK (≤3%)
50 mm²151 A118 A1.16 V (0.5%)228.8 V1.91 V (0.83%)34.7 W✓ OK (≤3%)
70 mm²192 A150 A0.83 V (0.36%)229.2 V1.36 V (0.59%)24.8 W✓ OK (≤3%)
95 mm²232 A181 A0.61 V (0.26%)229.4 V1.0 V (0.44%)18.2 W✓ OK (≤3%)
120 mm²269 A210 A0.48 V (0.21%)229.5 V0.79 V (0.35%)14.4 W✓ OK (≤3%)
150 mm²309 A241 A0.39 V (0.17%)229.6 V0.64 V (0.28%)11.6 W✓ OK (≤3%)
185 mm²353 A275 A0.31 V (0.14%)229.7 V0.52 V (0.22%)9.4 W✓ OK (≤3%)
240 mm²415 A324 A0.24 V (0.1%)229.8 V0.4 V (0.17%)7.2 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.08%)229.8 V0.32 V (0.14%)5.8 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.06%)229.9 V0.24 V (0.1%)4.3 W✓ OK (≤3%)

FAQ — Kabelarea för 30 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 30A vid 45 meter (230V)?

För 30 Ampere över 45 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (5.78V / 2.51%).

Hur stor effekt motsvarar 30A vid 230V?

Det motsvarar 6.9 kW med en rekommenderad säkring på 30A.