⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 30 Ampere vid 10 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 30 A över 10 m vid 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 3.21V (1.4%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 3.53V (1.53%)
Voltage at Load226.8 VLine Loss: 96.3 W
Max Power & Breaker6.9 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8.56 V (3.72%)221.4 V14.12 V (6.14%)256.8 WDrop High
2.5 mm²24 A18 A5.14 V (2.23%)224.9 V8.47 V (3.68%)154.1 WDrop High
4 mm²32 A25 A3.21 V (1.4%)226.8 V5.29 V (2.3%)96.3 W✓ OK (≤3%)
6 mm²41 A32 A2.14 V (0.93%)227.9 V3.53 V (1.53%)64.2 W✓ OK (≤3%)
10 mm²57 A44 A1.28 V (0.56%)228.7 V2.12 V (0.92%)38.5 W✓ OK (≤3%)
16 mm²76 A59 A0.8 V (0.35%)229.2 V1.32 V (0.58%)24.1 W✓ OK (≤3%)
25 mm²101 A78 A0.51 V (0.22%)229.5 V0.85 V (0.37%)15.4 W✓ OK (≤3%)
35 mm²125 A97 A0.37 V (0.16%)229.6 V0.61 V (0.26%)11.0 W✓ OK (≤3%)
50 mm²151 A118 A0.26 V (0.11%)229.7 V0.42 V (0.18%)7.7 W✓ OK (≤3%)
70 mm²192 A150 A0.18 V (0.08%)229.8 V0.3 V (0.13%)5.5 W✓ OK (≤3%)
95 mm²232 A181 A0.14 V (0.06%)229.9 V0.22 V (0.1%)4.1 W✓ OK (≤3%)
120 mm²269 A210 A0.11 V (0.05%)229.9 V0.18 V (0.08%)3.2 W✓ OK (≤3%)
150 mm²309 A241 A0.09 V (0.04%)229.9 V0.14 V (0.06%)2.6 W✓ OK (≤3%)
185 mm²353 A275 A0.07 V (0.03%)229.9 V0.11 V (0.05%)2.1 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.02%)229.9 V0.09 V (0.04%)1.6 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.02%)230.0 V0.07 V (0.03%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)230.0 V0.05 V (0.02%)1.0 W✓ OK (≤3%)

FAQ — Kabelarea för 30 Ampere vid 10 Meter (230V)

Vilken kabelarea krävs för 30A vid 10 meter (230V)?

För 30 Ampere över 10 meter vid 230V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (3.21V / 1.4%).

Hur stor effekt motsvarar 30A vid 230V?

Det motsvarar 6.9 kW med en rekommenderad säkring på 30A.