Kabelarea för 32 Ampere vid 400 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 400 m vid 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 5.77V (2.51%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 6.02V (2.62%)
Voltage at Load224.2 VLine Loss: 184.5 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A365.23 V (158.79%)0.0 V602.45 V (261.94%)11687.3 WDrop High
2.5 mm²24 A18 A219.14 V (95.28%)10.9 V361.47 V (157.16%)7012.4 WDrop High
4 mm²32 A25 A136.96 V (59.55%)93.0 V225.92 V (98.23%)4382.7 WDrop High
6 mm²41 A32 A91.31 V (39.7%)138.7 V150.61 V (65.48%)2921.8 WDrop High
10 mm²57 A44 A54.78 V (23.82%)175.2 V90.37 V (39.29%)1753.1 WDrop High
16 mm²76 A59 A34.24 V (14.89%)195.8 V56.48 V (24.56%)1095.7 WDrop High
25 mm²101 A78 A21.91 V (9.53%)208.1 V36.15 V (15.72%)701.2 WDrop High
35 mm²125 A97 A15.65 V (6.81%)214.3 V25.82 V (11.23%)500.9 WDrop High
50 mm²151 A118 A10.96 V (4.76%)219.0 V18.07 V (7.86%)350.6 W~ ≤5%
70 mm²192 A150 A7.83 V (3.4%)222.2 V12.91 V (5.61%)250.4 W~ ≤5%
95 mm²232 A181 A5.77 V (2.51%)224.2 V9.51 V (4.14%)184.5 W✓ OK (≤3%)
120 mm²269 A210 A4.57 V (1.98%)225.4 V7.53 V (3.27%)146.1 W✓ OK (≤3%)
150 mm²309 A241 A3.65 V (1.59%)226.3 V6.02 V (2.62%)116.9 W✓ OK (≤3%)
185 mm²353 A275 A2.96 V (1.29%)227.0 V4.88 V (2.12%)94.8 W✓ OK (≤3%)
240 mm²415 A324 A2.28 V (0.99%)227.7 V3.77 V (1.64%)73.0 W✓ OK (≤3%)
300 mm²477 A372 A1.83 V (0.79%)228.2 V3.01 V (1.31%)58.4 W✓ OK (≤3%)
400 mm²570 A445 A1.37 V (0.6%)228.6 V2.26 V (0.98%)43.8 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 400 Meter (230V)

Vilken kabelarea krävs för 32A vid 400 meter (230V)?

För 32 Ampere över 400 meter vid 230V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (5.77V / 2.51%).

Hur stor effekt motsvarar 32A vid 230V?

Det motsvarar 7.36 kW med en rekommenderad säkring på 32A.