Kabelarea för 80 Ampere vid 400 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 80 A över 400 m vid 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 5.71V (2.48%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.65V (2.46%)
Voltage at Load224.3 VLine Loss: 456.5 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A913.07 V (396.99%)0.0 V1506.13 V (654.84%)73045.3 WDrop High
2.5 mm²24 A18 A547.84 V (238.19%)0.0 V903.68 V (392.9%)43827.2 WDrop High
4 mm²32 A25 A342.4 V (148.87%)0.0 V564.8 V (245.57%)27392.0 WDrop High
6 mm²41 A32 A228.27 V (99.25%)1.7 V376.53 V (163.71%)18261.3 WDrop High
10 mm²57 A44 A136.96 V (59.55%)93.0 V225.92 V (98.23%)10956.8 WDrop High
16 mm²76 A59 A85.6 V (37.22%)144.4 V141.2 V (61.39%)6848.0 WDrop High
25 mm²101 A78 A54.78 V (23.82%)175.2 V90.37 V (39.29%)4382.7 WDrop High
35 mm²125 A97 A39.13 V (17.01%)190.9 V64.55 V (28.06%)3130.5 WDrop High
50 mm²151 A118 A27.39 V (11.91%)202.6 V45.18 V (19.65%)2191.4 WDrop High
70 mm²192 A150 A19.57 V (8.51%)210.4 V32.27 V (14.03%)1565.3 WDrop High
95 mm²232 A181 A14.42 V (6.27%)215.6 V23.78 V (10.34%)1153.3 WDrop High
120 mm²269 A210 A11.41 V (4.96%)218.6 V18.83 V (8.19%)913.1 W~ ≤5%
150 mm²309 A241 A9.13 V (3.97%)220.9 V15.06 V (6.55%)730.5 W~ ≤5%
185 mm²353 A275 A7.4 V (3.22%)222.6 V12.21 V (5.31%)592.3 W~ ≤5%
240 mm²415 A324 A5.71 V (2.48%)224.3 V9.41 V (4.09%)456.5 W✓ OK (≤3%)
300 mm²477 A372 A4.57 V (1.98%)225.4 V7.53 V (3.27%)365.2 W✓ OK (≤3%)
400 mm²570 A445 A3.42 V (1.49%)226.6 V5.65 V (2.46%)273.9 W✓ OK (≤3%)

FAQ — Kabelarea för 80 Ampere vid 400 Meter (230V)

Vilken kabelarea krävs för 80A vid 400 meter (230V)?

För 80 Ampere över 400 meter vid 230V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (5.71V / 2.48%).

Hur stor effekt motsvarar 80A vid 230V?

Det motsvarar 18.4 kW med en rekommenderad säkring på 80A.