Kabelarea för 32 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 80 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.16V (2.25%)
Voltage at Load223.2 VLine Loss: 219.1 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A73.05 V (31.76%)157.0 V120.49 V (52.39%)2337.5 WDrop High
2.5 mm²24 A18 A43.83 V (19.06%)186.2 V72.29 V (31.43%)1402.5 WDrop High
4 mm²32 A25 A27.39 V (11.91%)202.6 V45.18 V (19.65%)876.5 WDrop High
6 mm²41 A32 A18.26 V (7.94%)211.7 V30.12 V (13.1%)584.4 WDrop High
10 mm²57 A44 A10.96 V (4.76%)219.0 V18.07 V (7.86%)350.6 W~ ≤5%
16 mm²76 A59 A6.85 V (2.98%)223.2 V11.3 V (4.91%)219.1 W✓ OK (≤3%)
25 mm²101 A78 A4.38 V (1.91%)225.6 V7.23 V (3.14%)140.2 W✓ OK (≤3%)
35 mm²125 A97 A3.13 V (1.36%)226.9 V5.16 V (2.25%)100.2 W✓ OK (≤3%)
50 mm²151 A118 A2.19 V (0.95%)227.8 V3.61 V (1.57%)70.1 W✓ OK (≤3%)
70 mm²192 A150 A1.57 V (0.68%)228.4 V2.58 V (1.12%)50.1 W✓ OK (≤3%)
95 mm²232 A181 A1.15 V (0.5%)228.8 V1.9 V (0.83%)36.9 W✓ OK (≤3%)
120 mm²269 A210 A0.91 V (0.4%)229.1 V1.51 V (0.65%)29.2 W✓ OK (≤3%)
150 mm²309 A241 A0.73 V (0.32%)229.3 V1.2 V (0.52%)23.4 W✓ OK (≤3%)
185 mm²353 A275 A0.59 V (0.26%)229.4 V0.98 V (0.42%)19.0 W✓ OK (≤3%)
240 mm²415 A324 A0.46 V (0.2%)229.5 V0.75 V (0.33%)14.6 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.16%)229.6 V0.6 V (0.26%)11.7 W✓ OK (≤3%)
400 mm²570 A445 A0.27 V (0.12%)229.7 V0.45 V (0.2%)8.8 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 32A vid 80 meter (230V)?

För 32 Ampere över 80 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (6.85V / 2.98%).

Hur stor effekt motsvarar 32A vid 230V?

Det motsvarar 7.36 kW med en rekommenderad säkring på 32A.