Kabelarea för 16 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 80 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.48V (2.38%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.65V (2.46%)
Voltage at Load224.5 VLine Loss: 87.7 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A36.52 V (15.88%)193.5 V60.25 V (26.19%)584.4 WDrop High
2.5 mm²24 A18 A21.91 V (9.53%)208.1 V36.15 V (15.72%)350.6 WDrop High
4 mm²32 A25 A13.7 V (5.95%)216.3 V22.59 V (9.82%)219.1 WDrop High
6 mm²41 A32 A9.13 V (3.97%)220.9 V15.06 V (6.55%)146.1 W~ ≤5%
10 mm²57 A44 A5.48 V (2.38%)224.5 V9.04 V (3.93%)87.7 W✓ OK (≤3%)
16 mm²76 A59 A3.42 V (1.49%)226.6 V5.65 V (2.46%)54.8 W✓ OK (≤3%)
25 mm²101 A78 A2.19 V (0.95%)227.8 V3.61 V (1.57%)35.1 W✓ OK (≤3%)
35 mm²125 A97 A1.57 V (0.68%)228.4 V2.58 V (1.12%)25.0 W✓ OK (≤3%)
50 mm²151 A118 A1.1 V (0.48%)228.9 V1.81 V (0.79%)17.5 W✓ OK (≤3%)
70 mm²192 A150 A0.78 V (0.34%)229.2 V1.29 V (0.56%)12.5 W✓ OK (≤3%)
95 mm²232 A181 A0.58 V (0.25%)229.4 V0.95 V (0.41%)9.2 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.2%)229.5 V0.75 V (0.33%)7.3 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.16%)229.6 V0.6 V (0.26%)5.8 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.13%)229.7 V0.49 V (0.21%)4.7 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.1%)229.8 V0.38 V (0.16%)3.7 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.08%)229.8 V0.3 V (0.13%)2.9 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.06%)229.9 V0.23 V (0.1%)2.2 W✓ OK (≤3%)

FAQ — Kabelarea för 16 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 16A vid 80 meter (230V)?

För 16 Ampere över 80 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (5.48V / 2.38%).

Hur stor effekt motsvarar 16A vid 230V?

Det motsvarar 3.68 kW med en rekommenderad säkring på 16A.