Kabelarea för 32 Ampere vid 90 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 90 m vid 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 4.93V (2.14%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.81V (2.53%)
Voltage at Load225.1 VLine Loss: 157.8 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A82.18 V (35.73%)147.8 V135.55 V (58.94%)2629.6 WDrop High
2.5 mm²24 A18 A49.31 V (21.44%)180.7 V81.33 V (35.36%)1577.8 WDrop High
4 mm²32 A25 A30.82 V (13.4%)199.2 V50.83 V (22.1%)986.1 WDrop High
6 mm²41 A32 A20.54 V (8.93%)209.5 V33.89 V (14.73%)657.4 WDrop High
10 mm²57 A44 A12.33 V (5.36%)217.7 V20.33 V (8.84%)394.4 WDrop High
16 mm²76 A59 A7.7 V (3.35%)222.3 V12.71 V (5.53%)246.5 W~ ≤5%
25 mm²101 A78 A4.93 V (2.14%)225.1 V8.13 V (3.54%)157.8 W✓ OK (≤3%)
35 mm²125 A97 A3.52 V (1.53%)226.5 V5.81 V (2.53%)112.7 W✓ OK (≤3%)
50 mm²151 A118 A2.47 V (1.07%)227.5 V4.07 V (1.77%)78.9 W✓ OK (≤3%)
70 mm²192 A150 A1.76 V (0.77%)228.2 V2.9 V (1.26%)56.3 W✓ OK (≤3%)
95 mm²232 A181 A1.3 V (0.56%)228.7 V2.14 V (0.93%)41.5 W✓ OK (≤3%)
120 mm²269 A210 A1.03 V (0.45%)229.0 V1.69 V (0.74%)32.9 W✓ OK (≤3%)
150 mm²309 A241 A0.82 V (0.36%)229.2 V1.36 V (0.59%)26.3 W✓ OK (≤3%)
185 mm²353 A275 A0.67 V (0.29%)229.3 V1.1 V (0.48%)21.3 W✓ OK (≤3%)
240 mm²415 A324 A0.51 V (0.22%)229.5 V0.85 V (0.37%)16.4 W✓ OK (≤3%)
300 mm²477 A372 A0.41 V (0.18%)229.6 V0.68 V (0.29%)13.1 W✓ OK (≤3%)
400 mm²570 A445 A0.31 V (0.13%)229.7 V0.51 V (0.22%)9.9 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 90 Meter (230V)

Vilken kabelarea krävs för 32A vid 90 meter (230V)?

För 32 Ampere över 90 meter vid 230V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (4.93V / 2.14%).

Hur stor effekt motsvarar 32A vid 230V?

Det motsvarar 7.36 kW med en rekommenderad säkring på 32A.