⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 200 Ampere vid 90 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 200 A över 90 m vid 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 6.87V (2.99%)
Voltage at Load223.6 VLine Loss: 1284.0 W
Max Power & Breaker46.0 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A513.6 V (223.3%)0.0 V847.2 V (368.35%)102720.0 WDrop High
2.5 mm²24 A18 A308.16 V (133.98%)0.0 V508.32 V (221.01%)61632.0 WDrop High
4 mm²32 A25 A192.6 V (83.74%)37.4 V317.7 V (138.13%)38520.0 WDrop High
6 mm²41 A32 A128.4 V (55.83%)101.6 V211.8 V (92.09%)25680.0 WDrop High
10 mm²57 A44 A77.04 V (33.5%)153.0 V127.08 V (55.25%)15408.0 WDrop High
16 mm²76 A59 A48.15 V (20.93%)181.8 V79.42 V (34.53%)9630.0 WDrop High
25 mm²101 A78 A30.82 V (13.4%)199.2 V50.83 V (22.1%)6163.2 WDrop High
35 mm²125 A97 A22.01 V (9.57%)208.0 V36.31 V (15.79%)4402.3 WDrop High
50 mm²151 A118 A15.41 V (6.7%)214.6 V25.42 V (11.05%)3081.6 WDrop High
70 mm²192 A150 A11.01 V (4.79%)219.0 V18.15 V (7.89%)2201.1 WDrop High
95 mm²232 A181 A8.11 V (3.53%)221.9 V13.38 V (5.82%)1621.9 W~ ≤5%
120 mm²269 A210 A6.42 V (2.79%)223.6 V10.59 V (4.6%)1284.0 W✓ OK (≤3%)
150 mm²309 A241 A5.14 V (2.23%)224.9 V8.47 V (3.68%)1027.2 W✓ OK (≤3%)
185 mm²353 A275 A4.16 V (1.81%)225.8 V6.87 V (2.99%)832.9 W✓ OK (≤3%)
240 mm²415 A324 A3.21 V (1.4%)226.8 V5.29 V (2.3%)642.0 W✓ OK (≤3%)
300 mm²477 A372 A2.57 V (1.12%)227.4 V4.24 V (1.84%)513.6 W✓ OK (≤3%)
400 mm²570 A445 A1.93 V (0.84%)228.1 V3.18 V (1.38%)385.2 W✓ OK (≤3%)

FAQ — Kabelarea för 200 Ampere vid 90 Meter (230V)

Vilken kabelarea krävs för 200A vid 90 meter (230V)?

För 200 Ampere över 90 meter vid 230V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (6.42V / 2.79%).

Hur stor effekt motsvarar 200A vid 230V?

Det motsvarar 46.0 kW med en rekommenderad säkring på 200A.