⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 325 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 325 A över 45 m vid 230V.

Copper Cable (≤3% Drop)185 mm²Drop: 3.38V (1.47%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 3.44V (1.5%)
Voltage at Load226.6 VLine Loss: 1099.6 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A417.3 V (181.43%)0.0 V688.35 V (299.28%)135622.5 WDrop High
2.5 mm²24 A18 A250.38 V (108.86%)0.0 V413.01 V (179.57%)81373.5 WDrop High
4 mm²32 A25 A156.49 V (68.04%)73.5 V258.13 V (112.23%)50858.4 WDrop High
6 mm²41 A32 A104.33 V (45.36%)125.7 V172.09 V (74.82%)33905.6 WDrop High
10 mm²57 A44 A62.59 V (27.22%)167.4 V103.25 V (44.89%)20343.4 WDrop High
16 mm²76 A59 A39.12 V (17.01%)190.9 V64.53 V (28.06%)12714.6 WDrop High
25 mm²101 A78 A25.04 V (10.89%)205.0 V41.3 V (17.96%)8137.3 WDrop High
35 mm²125 A97 A17.88 V (7.78%)212.1 V29.5 V (12.83%)5812.4 WDrop High
50 mm²151 A118 A12.52 V (5.44%)217.5 V20.65 V (8.98%)4068.7 WDrop High
70 mm²192 A150 A8.94 V (3.89%)221.1 V14.75 V (6.41%)2906.2 WDrop High
95 mm²232 A181 A6.59 V (2.86%)223.4 V10.87 V (4.73%)2141.4 WDrop High
120 mm²269 A210 A5.22 V (2.27%)224.8 V8.6 V (3.74%)1695.3 WDrop High
150 mm²309 A241 A4.17 V (1.81%)225.8 V6.88 V (2.99%)1356.2 WDrop High
185 mm²353 A275 A3.38 V (1.47%)226.6 V5.58 V (2.43%)1099.6 W✓ OK (≤3%)
240 mm²415 A324 A2.61 V (1.13%)227.4 V4.3 V (1.87%)847.6 W✓ OK (≤3%)
300 mm²477 A372 A2.09 V (0.91%)227.9 V3.44 V (1.5%)678.1 W✓ OK (≤3%)
400 mm²570 A445 A1.56 V (0.68%)228.4 V2.58 V (1.12%)508.6 W✓ OK (≤3%)

FAQ — Kabelarea för 325 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 325A vid 45 meter (230V)?

För 325 Ampere över 45 meter vid 230V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (3.38V / 1.47%).

Hur stor effekt motsvarar 325A vid 230V?

Det motsvarar 74.75 kW med en rekommenderad säkring på 350A.