Kabelarea för 325 Ampere vid 70 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 325 A över 70 m vid 230V.

Copper Cable (≤3% Drop)185 mm²Drop: 5.26V (2.29%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 5.35V (2.33%)
Voltage at Load224.7 VLine Loss: 1710.6 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A649.13 V (282.23%)0.0 V1070.77 V (465.55%)210968.3 WDrop High
2.5 mm²24 A18 A389.48 V (169.34%)0.0 V642.46 V (279.33%)126581.0 WDrop High
4 mm²32 A25 A243.43 V (105.84%)0.0 V401.54 V (174.58%)79113.1 WDrop High
6 mm²41 A32 A162.28 V (70.56%)67.7 V267.69 V (116.39%)52742.1 WDrop High
10 mm²57 A44 A97.37 V (42.33%)132.6 V160.62 V (69.83%)31645.2 WDrop High
16 mm²76 A59 A60.86 V (26.46%)169.1 V100.38 V (43.65%)19778.3 WDrop High
25 mm²101 A78 A38.95 V (16.93%)191.1 V64.25 V (27.93%)12658.1 WDrop High
35 mm²125 A97 A27.82 V (12.1%)202.2 V45.89 V (19.95%)9041.5 WDrop High
50 mm²151 A118 A19.47 V (8.47%)210.5 V32.12 V (13.97%)6329.1 WDrop High
70 mm²192 A150 A13.91 V (6.05%)216.1 V22.95 V (9.98%)4520.8 WDrop High
95 mm²232 A181 A10.25 V (4.46%)219.8 V16.91 V (7.35%)3331.1 WDrop High
120 mm²269 A210 A8.11 V (3.53%)221.9 V13.38 V (5.82%)2637.1 WDrop High
150 mm²309 A241 A6.49 V (2.82%)223.5 V10.71 V (4.66%)2109.7 WDrop High
185 mm²353 A275 A5.26 V (2.29%)224.7 V8.68 V (3.77%)1710.6 W✓ OK (≤3%)
240 mm²415 A324 A4.06 V (1.76%)225.9 V6.69 V (2.91%)1318.6 W✓ OK (≤3%)
300 mm²477 A372 A3.25 V (1.41%)226.8 V5.35 V (2.33%)1054.8 W✓ OK (≤3%)
400 mm²570 A445 A2.43 V (1.06%)227.6 V4.02 V (1.75%)791.1 W✓ OK (≤3%)

FAQ — Kabelarea för 325 Ampere vid 70 Meter (230V)

Vilken kabelarea krävs för 325A vid 70 meter (230V)?

För 325 Ampere över 70 meter vid 230V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (5.26V / 2.29%).

Hur stor effekt motsvarar 325A vid 230V?

Det motsvarar 74.75 kW med en rekommenderad säkring på 350A.